TROUBLESHOOTING

6.1

Purpose of troubleshooting

The  purpose  of  troubleshooting  is  primarily  to  determine  whether  problems  are  caused  by  the  frequency
converter  or  external  devices.  It  is  also  possible  that  a  faulty  external  device  has  caused  damage  to  the
frequency converter. In that case it is very important to repair or change any faulty devices to prevent recurring
problems.

6.2

Problems and solutions

Sr.

no.

Product

Suggested solution

1

The frequency converter is on
READY status but motor does not
run or just jerks but control voltage
can be measured from the
terminals.

Make sure that the front resistors on the control voltage circuit
have been removed or by-passed according to the instructions
in 

Control voltage front resistors (page 11)

.

2

The frequency converter does not
start (not in READY status) when it
is started.

• Measure the main voltage between terminals L1, L2 and L3.

See electrical drawings for the correct value.

• Make sure that there are no devices causing disturbance

connected to the same voltage supply as the crane, such as
big motors or welding devices.

• Make sure all motor cables have proper connection.
• Make sure that no limit switch or operation is not active.
• Measure the control voltage in direction command terminal 1

(DI1) and terminal 2 (DI2) against the common (terminal 7).
Voltage should increase when button is pushed on the
controller.

When the EMC screw is connected, the frequency
converter has RC filters connected to the power
supply side to reduce disturbance to the network.
The capacitors of these filters may cause the
RCD (Residual Current Device) to trip. Therefore,
using RCD with frequency converter controlled
cranes is not recommended.

3

The motor runs poorly: trolley/bridge
does not move as it supposed to
move.

• Check that the load is not over nominal.
• Check that all cables are correctly connected and not loose.
• Check that all motor parameters are correctly set.
• Check that the U/f-curve parameters (P4.2, P4.3 and P4.4) are

correctly set.

• Check that the motor’s brake opens completely.

6.3

Fault codes and alarms

When the frequency converter detects an unacceptable situation it stops the current movement and indicates a
warning or fault code. First digits of the fault code indicates the order f the code, e.g. F1 means the latest fault.
Next two digits are indicating the fault code. At active fault situation FAULT arrow and fault code are blinking. If
there are several active faults, they all are blinking in history browsing.

Some of the faults are reset automatically by the software, while others may require the frequency converter to
be powered down. The causes of the fault(s) must be resolved and both drive commands have to be on the
OFF position for 0.5s before the motor can be started again. In a case of over current fault the supply voltage
must be switched off and back on before it is possible to resume operation.

The warning and fault code numbers and corresponding warnings and faults, possible causes and suggested
solutions are listed in the following table.

020145en / Revision D / 2015-04-29

26/31

This document and the information contained herein, is the exclusive property of Konecranes Plc. and represents a non-public, confidential and proprietary trade secret that may not be
reproduced, disclosed to other parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc.
Copyright 

©

 (2014) Konecranes Plc. All rights reserved.

Summary of Contents for DMCS022

Page 1: ...ned herein is the exclusive property of Konecranes Plc and represents a non public confidential and proprietary trade secret that may not be reproduced disclosed to other parties altered or otherwise...

Page 2: ...trol voltage front resistor 11 4 5 New frequency controller installation 12 5 COMMISSIONING 19 5 1 Old inverter parameter settings 19 5 2 Motor type 19 5 3 Traveling motor rating plate values 19 5 4 S...

Page 3: ...the upgrade kit usage This upgrade kit is designed only for DynADrive 022 frequency converter 1 3 Waste treatment and recycling of removed material The removed parts and packaging material shall be r...

Page 4: ...ing live electrical circuit can cause serious injury Even though main switch is turned off there may still be voltage inside electrical devices such as inverters Wait at least 5 minutes before opening...

Page 5: ...1 pcs Part 4 Wire end ferrule 2 5mm 10 pcs Part 5 M5 x 10 Flanged screw 10 pcs 020145en Revision D 2015 04 29 5 31 This document and the information contained herein is the exclusive property of Kone...

Page 6: ...04 29 6 31 This document and the information contained herein is the exclusive property of Konecranes Plc and represents a non public confidential and proprietary trade secret that may not be reproduc...

Page 7: ...limit direction 1 4 Common slowdown Slowdown Stop limit direction 1 4 Slowdown Stop limit direction 2 5 Common stop Slowdown Stop limit direction 2 5 Common DI1 5 6 Motor temperature protection Exter...

Page 8: ...r package KC310 KC330 whereas DynA45 has an internal EMC filter in the power supply By default the EMC level of the frequency converter is set to N by the manufacturer If the mains network is non grou...

Page 9: ...perty of Konecranes Plc and represents a non public confidential and proprietary trade secret that may not be reproduced disclosed to other parties altered or otherwise employed in any manner whatsoev...

Page 10: ...roller WARNING High voltage inside the Frequency converter Wait for at least five minutes after the voltage supply has been switched of before taking any service actions 3 DynA45 006 has an internal E...

Page 11: ...r 6 must be connected to OL10 via MSL 5 Loosen and remove the screws 4 pcs holding the DynADrive 022 Remove the DynADrive 022 and the EMC filter from the enclosure Note The old screws are self tapping...

Page 12: ...resistor wire from the braking resistor to the cubicle 2 Put 4 pcs size M5 x 10 Flanged installation screws into back plate Leave screws loose The installation rack has slotted screw holes 020145en Re...

Page 13: ...nimum of 2 5 mm This extra grounding wire is not delivered with the package 8 If the DynADrive 022 has an external braking resistor Remove the internal braking resistor wires and connect the braking r...

Page 14: ...re 2 New inverter MS2 stop Digital input 5 in DynA45 will be deactivated No connection is needed 020145en Revision D 2015 04 29 14 31 This document and the information contained herein is the exclusiv...

Page 15: ...l be deactivated No connection is needed Variation 3 EP2 MS2 stop 020145en Revision D 2015 04 29 15 31 This document and the information contained herein is the exclusive property of Konecranes Plc an...

Page 16: ...n D 2015 04 29 16 31 This document and the information contained herein is the exclusive property of Konecranes Plc and represents a non public confidential and proprietary trade secret that may not b...

Page 17: ...ies 020145en Revision D 2015 04 29 17 31 This document and the information contained herein is the exclusive property of Konecranes Plc and represents a non public confidential and proprietary trade s...

Page 18: ...formation contained herein is the exclusive property of Konecranes Plc and represents a non public confidential and proprietary trade secret that may not be reproduced disclosed to other parties alter...

Page 19: ...ther use on commissioning Name Motor rating plate value Motor Nom Volt V Motor Nom Freq Hz Motor Nom Speed rpm Motor Nom Curr A Nom Magnetizing Curr A Motor Cos Phi 5 4 Setting up the new inverter par...

Page 20: ...ynADrive 022 Minimum frequency Hz To P1 2 Maximum Frequency Hz To P1 3 Switch S1 1 2 3 4 0 0 0 0 29 100 0 0 0 1 14 50 0 0 1 0 23 62 0 0 1 1 10 54 0 1 0 0 32 80 0 1 0 1 12 58 0 1 1 0 16 66 0 1 1 1 18 7...

Page 21: ...imum frequency Hz To P1 2 Maximum Frequency Hz To P1 3 Switch S1 1 2 3 4 0 0 0 0 15 50 0 0 0 1 7 25 0 0 1 0 12 31 0 0 1 1 5 27 0 1 0 0 16 40 0 1 0 1 6 29 0 1 1 0 8 33 0 1 1 1 9 35 1 0 0 0 25 58 1 0 0...

Page 22: ...2015 04 29 22 31 This document and the information contained herein is the exclusive property of Konecranes Plc and represents a non public confidential and proprietary trade secret that may not be re...

Page 23: ...s DynADrive 022 Acceleration and deceleration Ramp Time s Switch S3 1 2 3 4 0 0 0 0 2 5 0 0 0 1 3 5 0 0 1 0 3 0 0 1 1 5 0 1 0 0 2 0 1 0 1 8 0 1 1 0 1 0 1 1 1 7 5 1 0 0 0 1 5 1 0 0 1 4 1 0 1 0 7 1 0 1...

Page 24: ...f mid frequency in Hz P4 4 Rs voltage drop in percent of motor nominal voltage Table 8 Motor control parameters Compact brake motors DynADrive 022 DynA45 006 Switch S4 Parameter 1 2 3 4 P3 2 P4 1 P4 2...

Page 25: ...to set travel limits to work After setting the parameters test the limit functions Old DynADrive 022 inverter control board connections Original limit settings DynA45 006 parameter P6 2 P6 3 P6 4 X1...

Page 26: ...th frequency converter controlled cranes is not recommended 3 The motor runs poorly trolley bridge does not move as it supposed to move Check that the load is not over nominal Check that all cables ar...

Page 27: ...lem recurs replace inverter B 24 Counter fault Internal counter error Switch off supply voltage If problem recurs replace inverter B 25 API Microprocessor Watchdog Internal watchdog error Switch off s...

Page 28: ...ion wiring C 58 Overvoltage Regulator Timeout Overvoltage regulator has been active for 5 sec C 59 Overvoltage at Start Too high supply voltage Measure supply voltage and check hoist supply voltage fr...

Page 29: ...ror detected in ROB1 relay test circuit or the main contactor Check main contactor circuit wiring If problem recurs replace inverter A 71 Brake control Error detected in brake control circuit Check re...

Page 30: ...of range Check repair load sensor wiring Check replace load sensor C Resetting column explanation A E stop activation deactivation B Hoist supply voltage switch OFF ON C Automatic when fault situatio...

Page 31: ...d in CAN bus has an active fault 93 CCU activation Controlled common use activation Another device that is connected in CAN bus has caused the stopping 020145en Revision D 2015 04 29 31 31 This docume...

Reviews: