Kongsberg ACS500
Sequence already executing
– A Valve sequence is already performing. Wait for status
from SCU.
Automatic shutdown
, Optional function. This should not be displayed when function is
not available. – Check configuration settings.
SW watchdog
, error bit from the SCU regarding software watchdog operation. – Wait 1
minute to power down the SCU and perform a Read System Status operation. Check if
the error messages are still present. Report incident for a possible service operation.
Low battery
, warning bit from SCU. – Perform a normal % Read battery command
status in order to decide the remaining battery capacity of the SCU battery. When a
single battery has less than 20 % capacity left, a yellow background in % window is
shown. It is time to plan for a battery change. When the window is red it is less than
10% remaining capacity. Change battery when it is possible, alternatively try to operate
on the other SCU unit if this battery has a higher remaining capacity.
Current leakage
, If this error message is displayed, then the SCU is not allowed to
perform a Valve operation towards the solenoids. . – Try to read the actual current value
in More Status. Check battery status. If possible check the other SCU unit. Possible
failure could be caused by water leakage of different kinds.
SERVICE may be required!
Current overflow
, Error detected, Valve operation will not be performed correctly.
Solenoid current drive will be stopped in order not to damage electronics and solenoids.
– Try to Read actual current value in More Status. Check battery status. If possible check
the other SCU unit. Possible failure could be caused by water leakage of different kinds.
SERVICE may be Required!
Parameter CRC
, Software CRC check in SCU indicates that the SCU is not properly
configured. – The SCU should be configured properly and tested on deck by using a
BOP Simulator. Service personnel assistance is required.
BOP status
Unknown
, status not available – Read System Status, see
on page 48.
ARMED
, SCU read back shows BOP is ARMED – Check if this is the expected status of
the BOP.
DISARMED
, SCU read back shows BOP is DISARMED – Check if this is the expected
status of the BOP.
56
397128/C
Summary of Contents for ACS500
Page 1: ...INSTRUCTION MANUAL ACS500 Acoustic Control System Gisma testport system...
Page 2: ......
Page 15: ...ACS500 System with interface cables 397128 C 13...
Page 38: ...Kongsberg ACS500 ACU Computer buttons on page 37 User interface on page 38 36 397128 C...
Page 71: ...Simulation and test 397128 C 69...
Page 113: ...Drawing file Dunking transducer unit outline dimensions 397128 C 111...
Page 114: ...Kongsberg ACS500 Acoustic Command Unit outline dimensions 112 397128 C...
Page 115: ...Drawing file Subsea Control Unit outline dimensions 397128 C 113...
Page 116: ...Kongsberg ACS500 Subsea Control Unit arrangement 114 397128 C...
Page 117: ...Drawing file Subsea Control Unit bracket 397128 C 115...
Page 118: ...Kongsberg ACS500 TDR30V 34GT Subsea transducer outline dimensions 116 397128 C...
Page 119: ...Drawing file External quad battery unit for SCU outline dimensions 397128 C 117...
Page 120: ...Kongsberg ACS500 Simulator outline dimensions 118 397128 C...
Page 138: ...Kongsberg ACS500 Appendix A Type approval certificate 136 397128 C...
Page 139: ...Appendix A Type approval certificate 397128 C 137...
Page 140: ...Kongsberg ACS500 138 397128 C...
Page 141: ...Appendix A Type approval certificate 397128 C 139...
Page 142: ...Kongsberg ACS500 140 397128 C...
Page 148: ...2016 Kongsberg Maritime...