Fire damper FSD-B-U / FSD-A-U FLD-S-U /
FLD-S-UD. Technical data
Selection chart FSD-B-U / FSD-A-U FLD-S-U / FLD-S-UD
Selection example:
For the given duct dimensions and technical data, we select a 1200 x 200 mm FSD-B-U damper. We use the table on the
previous page to find the following data:
A
L
= 0,24 m
2
k
p
= 1,8
kdB(A)= -2
The technical data to achieve a flow rate of 3500 m
3
/h is required.
Referring to the diagram above using this flow rate and the area o 0,24 m
2
, we obtain a Veff of 4 m/s. With this veocity
and taking into account the value of kp, we obtain:
Differential pressure: 30 Pa
Sound pressure level: 45 dB(A)
Applying L
wA
- dB(A) = 45+ (-2) = 43 dB(A)
Series FSD-FLD
10