background image

8

9

User Manual

8

User Manual

Display Panel

The Koolance display panel allows control and monitoring of various aspects of 
the cooling unit. 5 buttons are used, with directional arrows to navigate or change 
settings, and a center button to select/exit.

    • On the main screen, hold 

 for 3 seconds to change display units between 

      °C/°F and LPM/GPM.
    • You can exit any menu and return to the main screen by holding 

 

for 2 

       seconds.
    • To reset 

ALL

 settings to default, hold 

 + 

 for 3 seconds.

Main Menu

To enter the main menu, briefly press 

. The selected option will begin flashing. 

Use 

 and 

 to navigate this menu.

    TEMP SET

:  Temperature set-point adjustment

    ALARM SET

:  Alarm settings

    RELAY SET

:  Relay Trigger settings

    PUMP SET

:  Pump speed settings

    DISPLAY SET

:  LCD display settings

When in the top menu, press 

 to enter one of the above categories. To exit from 

here, press 

.

External Sensor

This unit provides a terminal on the rear for 
connecting a K-type thermocouple (not included) 
for external monitoring and temperature 
configuration.

Navigate Up,

Increase Setting

Navigate Down,

Decrease Setting

Navigate 

Left

Navigate 

Right

Enter/Exit

Under “TEMP SET”, you can select the active temperature sensor and set-point 
the chiller will try to follow. There are four temperature options to select from. 

Press 

 and 

 

to scroll among these options:

    LIQ TEMP

:  Liquid temperature (Range: 1 to 50°C)

    EXT TEMP

:  Rear sensor, if attached (Range: 1 to 149°C)

    LIQ-AMB

:  Delta-T between liquid & ambient (Range: -50 to 50°C)

    EXT-AMB

:  Delta-T between rear sensor & ambient (Range: -50 to 50°C)

The sensor currently displayed in this menu is what the chiller will follow.

Only one can be active. 

Press 

 to adjust the target temperature value using 

 

and 

. Below are some examples:

  LIQ TEMP= 28C  

Maintain coolant coming from the chiller at 28°C

  EXT TEMP= 50C  

Maintain the external sensor at 50°C (if attached)

  LIQ-AMB=  -5C  

Maintain a difference between the liquid and ambient

 

 

 

     air of -5°C (keep liquid 5°C below ambient)

  EXT-AMB=  5C  

Maintain a difference between the external sensor and

 

 

 

   ambient air of +5°C (keep sensor 5ºC above ambient)

Press

 

 

again to exit configuration of the sensor. Press 

 to return to the previous 

menu.

With these settings, it’s possible to set the liquid temperature below the environmental 
air temperature. If liquid temperatures reach the ambient dew point, condensation 
(water droplets) can form on tubing and cold plates connected to the chiller. Unless 
condensation is prepared for, 

it is recommended to keep the chiller on “LIQ-

AMB” with a minimum value of 0°C (which keeps liquid at ambient).

TEMP SET

CAUTION:

 This cooling system can chill liquid below the ambient air 

temperature, which may cause condensation to form on tubing and 
cold plates. It is highly recommended to keep the temperature at or 
above the ambient temperature. (See below for details.)

!

CAUTION:

 Do not use a temperature set-point that is below the 

coolant’s freezing point. This may damage the cooling unit and is not 
covered by the product warranty. It is recommended to always keep 
the temperature set-point at or above ambient temperature.

!

Summary of Contents for EXC-450

Page 1: ...Superior Liquid Cooling Systems English v1 0 www koolance com ISO 9001 Printed in Korea EXC 450 User s Manual EXC 450 User s Manual ...

Page 2: ...ation control life support or weapon launching control If these products are used in such hazardous environments Koolance Incorporated does not warrant them TRADEMARKS The Koolance name and logo are trademarks or registered trademarks of Koolance Inc Other company and product names used in this publication are for identification purposes only and may be trademarks or registered trademarks of their...

Page 3: ...vered by the product warranty CAUTION Always keep the chiller upright during operation Additionally THE UNIT MUST BE KEPT UPRIGHT FOR AT LEAST 24 HOURS BEFORE POWERING ON This is to allow enough oil to reach the compressor Powering on the unit too early can permanently damage the compressor and is not covered by the product warranty CAUTION This cooling system can chill liquid below the ambient ai...

Page 4: ...covered by the product warranty Positioning the System The chiller must be run upright at all times Upon arrival of this product via transport or courier shipping it must be kept upright FOR AT LEAST 24 HOURS BEFORE BEING POWERED ON to allow enough oil to reach the compressor OK NO NO External Fittings Install G 1 4 BSPP threaded fittings you have purchased into the Inlet and Outlet ports It s rec...

Page 5: ... to move it into the proper position before releasing Slowly fill the system with coolant To maintain the product warranty use only Koolance approved coolant Many alternative liquids and additives can cause permanent damage to the cooling unit through chemical reaction corrosion biological growth thermal expan sion viscosity etc Once all devices cold plates fittings etc have been connected with tu...

Page 6: ...a T between liquid ambient Range 50 to 50 C EXT AMB Delta T between rear sensor ambient Range 50 to 50 C The sensor currently displayed in this menu is what the chiller will follow Only one can be active Press to adjust the target temperature value using and Below are some examples LIQ TEMP 28C Maintain coolant coming from the chiller at 28 C EXT TEMP 50C Maintain the external sensor at 50 C if at...

Page 7: ...erature must be at least 1 C 1 2 F higher than the alarm temperature If an alarm temperature can not be increased first increase the relay temperature Likewise if a relay temperature can not be decreased first decrease the alarm temperature ALARM SET PUMP SET The pump speed can be manually set from 1 lowest to 10 highest PUMP 1 10 7LV Pump Speed Level The pump speed level will flash Press or to ad...

Page 8: ...the pump speed to 10 see PUMP SET to help push out the air If possible while the pump is running gently tilt your cold plates or other components connected to the chiller in various directions to assist with bleeding air from the cooling loop If it becomes necessary to tilt the chiller to assist with priming close the fill port and power off the unit before doing so 3 The temperature alarm sounds ...

Page 9: ...mage resulting from warranty service performed by a non authorized repair service No responsibility is assumed for any special incidental or consequential damages due to a defective Koolance product In order to obtain warranty service contact our RMA department for information The product must be shipped postage prepaid to an authorized Koolance service location It is suggested that for your prote...

Reviews: