This menu affects when the built-in audio alarm will sound. Upon entering the 
alarm menu, the temperature delta-t value will flash. 

Press 

 or 

 to adjust this 

value. Press

 

 

to accept and return to the previous menu.

    ALARM SET
    (TEMP SET) ± 5C

 

In the above example, the alarm will sound if the temperature exceeds a 5°C  
difference (+ or -) from the chiller’s currently active temperature sensor (see “TEMP 
SET”). The maximum delta-T setting range for the alarm is 49°C.

The regular audio alarm is a repeating beep. If a steady alarm tone is heard, this 
indicates the relay has also been triggered (see “RELAY SET”).

NOTE: The alarm temperature must be at least 1°C (1-2°F) lower than the relay 
temperature. If an alarm temperature can not be increased, first increase the relay 
temperature. Likewise, if a relay temperature can not be decreased, first decrease 
the alarm temperature.

RELAY SET

Rear terminals are provided for a temperature-
configurable relay. Wires can be connected as 
normally-open (NO), or normally-closed (NC), 
labeled below the terminals.

To adjust the relay trigger point, enter the “RELAY 
SET” menu.  

Press 

 or 

 to adjust this value. 

Press

 

 

to accept and return to the previous 

menu.

    RELAY SET
    (TEMP SET) ± 40C

In the above example, the relay will trigger if the temperature exceeds a 40°C  
difference (+ or -) from the chiller’s currently active temperature sensor (see “TEMP 
SET”). The maximum delta-T setting range for the relay is 50°C.

NOTE: The relay temperature must be at least 1°C (1-2°F) higher than the alarm 
temperature. If an alarm temperature can not be increased, first increase the relay 
temperature. Likewise, if a relay temperature can not be decreased, first decrease 
the alarm temperature.

ALARM SET

PUMP SET

The pump speed can be manually set from 1 (lowest) to 10 (highest):

    PUMP(1-10)    7LV

 :  Pump Speed Level

The pump speed level will flash. Press 

 or 

 to adjust. 

Press 

 

to return to the 

previous menu.

DISPLAY SET

The display settings configure which values you wish to appear on the front display 
and how they are shown:

    DISPLAY
    FIXED     CYCLIC

 :  Show 2 fixed values or cycle multiple values

The first option, “FIXED”, will flash. Press 

 or 

 to change between these 

options. Press 

 to configure one of the selections, or press 

 to exit. 

If “FIXED” 

is selected, two lines will be shown:

    LIQ SET         20C

 :  First line display option

    EXT TEMP    21.4C

 :  Second line display option

The first line will flash. Press 

 or 

 to change what this line will display:

    LIQ SET

 :  (Field varies) Shows current active sensor and user set-point

    AMB TEMP

 :  Shows ambient air temperature

    LIQ TEMP

 :  Shows reservoir liquid temperature

    EXT TEMP

 :  Shows external sensor temperature (if connected)

    FAN

 :  Shows condenser fan RPM

    PUMP

 :  Shows pump impeller RPM

    FLOW 

:  Shows liquid flow rate through the unit

Press

 

 to move to line 2, and similarly use

 

 or 

 to choose what will be 

displayed on the second line. Press

 

 again to exit.

WARNING

:

 The cooling system’s pump can not be run dry for any 

period of time. Never power-on the chiller without sufficient liquid in 
the reservoir. Dry-running (and thereby damaging the pump) is not 
covered under the Koolance product warranty.

!

Summary of Contents for EXC-800

Page 1: ...Superior Liquid Cooling Systems English v1 0 www koolance com ISO 9001 Printed in Korea EXC 800 User s Manual EXC 800 User s Manual...

Page 2: ...lear power core control airplane control air traffic control mass transport operation control life support or weapon launching control If these products are used in such hazardous environments Koolanc...

Page 3: ...and is not covered by the product warranty CAUTION Always keep the EXC 800 chiller upright during operation Additionally THE UNIT MUST BE KEPT UPRIGHT FOR AT LEAST 24 HOURS BEFORE POWERING ON This is...

Page 4: ...can permanently damage the compressor and is not covered by the product warranty Positioning the System The chiller must be run upright at all times Upon arrival of this product via transport or cour...

Page 5: ...n filling the system and keep all liquids away from electronics and power cables Keep the primaryAC power cable unplugged whenever filling or draining coolant Power on the cooling unit Set the pump to...

Page 6: ...T between liquid ambient Range 50 to 50 C EXT AMB Delta T between rear sensor ambient Range 50 to 50 C The sensor currently displayed in this menu is what the chiller will follow Only one can be acti...

Page 7: ...rature must be at least 1 C 1 2 F higher than the alarm temperature If an alarm temperature can not be increased first increase the relay temperature Likewise if a relay temperature can not be decreas...

Page 8: ...the pump speed to 10 see PUMP SET to help push out the air If possible while the pump is running gently tilt your cold plates or other components connected to the chiller in various directions to assi...

Page 9: ...age resulting from warranty service performed by a non authorized repair service No responsibility is assumed for any special incidental or consequential damages due to a defective Koolance product In...

Reviews: