7.4 Ensure the smoothness of drainpipes.   

7.5 Frequently observe the operation of the product. In case of any abnormal noise, smell or smog, 

cut off the power supply immediately and call for professionals for help. Do not restart the product 

before trouble is cleared.   

7.6 We will not be responsible for any accident incurred by failures of following the notices.   

8. Frequent troubleshooting 

Number 

Troubles 

Causes 

Solutions 

Strange  noise  under  the 
bottom shelf 

Fan blade broken. 

Power off and fix the blade. 

Non-refrigerating  in  spite 
of normal operation 
 

1. Unit off. 
2. Melting process. 
3. Refrigerant leaking 
4. Unit failure. 

1. Power on. 
2. Stop melting. 
3.  Patch  the  leak  and  refill 
refrigerant. 
4. Call for professionals. 

Weak  air  from  air  curtain, 
and 

higher 

cabinet 

temperature 

1.  Evaporator  blocked  by 
frost. 
2. Inside fan damaged. 
3.Too  low  set  point  of 
temperature controller. 
4.Vent blocked by storage 

1. Increase melting frequency. 
2. Replace the fan. 
3. Adjust the set point. 
4. Remove the storage. 

Normal  air  curtain,  but 
higher 

cabinet 

temperature 

1. Insufficient refrigerant. 
2.Too  high  set  point  of 
temperature controllers.   
3.Expansion value fails.   
4.Thewind  curtain  disturbed 
by strong air flow. 
5.  Ambient  temperature  or 
humidity beyond standards. 

1.Refill the refrigerant.   
2.Adjust  the  set  point  for  the 
temperature controller. 
3.Repair  or  replace  the  expansion 
valve. 
4. Removing the disturbing factors. 
5. Improve the conditions.   

Melting water overflown 

1.Heating  pipe  for  melting 
water damaged 
2. 

Water-level 

controller 

failure. 
3.  Ambient  temperature  or 
humidity beyond standards. 

1. Replace the heating pipe. 
2.Replace the water-level controller. 
3. Impove the conditions. 

Normal  air  curtain,  but 

periodical  fluctuation  of 
cabinet temperature   

1.Condenser contaminated. 
2. Poor venting of the unit. 
3.Heatprotection 

of 

compressor failure. 
4.Expansion  valve  blocked  by 
ice 
5. Expansion valve failure. 
6.  Temperature  controller 
failure. 

1. Clean the condenser. 
2. Improve the venting conditions. 
3. Replace the heat protection. 
4. Replace the drying filter. 
5. Replace the expansion valve. 
6. 

Replace 

the 

temperature 

controller. 