Service manual EKCO.T/EKCO.TM
10
Tab.1 Failures
Symptoms
Reason
Operation
Control panel
JOEJDBUPSTBSFPò
Power supply failure.
Check the mains and the main fuses.
$IFDLUIF85UFNQFSBUVSFDVUPò
Replace the control panel.
indicator "2" is blinking.
The flow value is „0” or is to low.
(below value of 12 l/min)
Heating is blocked.
Check the pump fuse on ZIO23 board.
Air lock in the heating system, solve the problem.
Deaerate the pump and the heating system.
Circulating pump is blocked.
Circulating pump is blocked. Make a manual pump
run. Use the screw to rotate the rotor.
Replace pump.
Flow sensor failure.
Replace flow sensor.
Room thermostat start heating
and the "3" indicator on the
DPOUSPMQBOFMJTOPUPò
The room thermostat wiring connection
failure.
Check the room thermostat wiring connection.
Room thermostat failure.
Replace room thermostat.
ZIO 23 failure.
Replace ZIO 23 board.
The "1" indicator is on
The boiler is heating only central heating
The three-way valve failure
Check the servo. Replace the servo of valve
ZIO 23 failure
Replace ZIO 23 board
DHW temperature is too low.
The boiler is heating only the heating
system.
5IFJOEJDBUPSJTPò
The DHWT thermostat or DHWT electronic
Sensor (DS 1820) failure
Replace DHWT thermostat or electronic sensor
(DS 1820)
ZIO 23 failure
Replace ZIO 23 board
Too low DHWT temperature settings
Set the higher temperature on the DHWT
thermostat or rise the DHWT temperature on the
control panel (for the electronic sensor DS 1820)
The supply temperature is too low
Heating box failure.
Check or replace heating box.
The NA connector is opened by the
superior device.
The "3" indicator does not blink
RP connector opened
Check the room thermostat
Control panel failure PSK.P4
Replace front panel
Control panel indicators
are blinking or temperature indicator is
blinking or the
return or supply temperature
JOEJDBUPSJTTIPXJOH¡$
Return or supply temperature sensor.
Use the right arrow to view the return inlet and
flow outlet temperature. If the „E” symbol or 99 is
displayed replace the required sensor.
(Nominal resistance of the temperature sensor
LȰBU¡$
Control panel failure
Replace the control panel PSK.P4
3.2
Failure modes of PSK.P4 front panel.
Summary of Contents for ECKO.TM
Page 1: ...1 KOSPEL S A KOSZALIN ul Olchowa 1 SERVICE MANUAL EKCO T ECKO TM 17 11 2020 ...
Page 5: ...5 Pic 1b EKCO TM boiler 5 01216 19 01220 23 00035 32 6 01217 ...
Page 7: ...7 Pic 2bConstruction of the boiler EKCO TM ...
Page 26: ...Service manual EKCO T EKCO TM 26 14 2 Pump Wilo Yonos Para alarm status Tab 7 Alarm status ...