13
4.2
Failure modes of PSK.P4 control panel.
Tab.3 Failures
"Faults” display view shows possible failures: flow failure, outdoor/room temperature sensor failure, inlet outlet boiler sensor
failure. The controller enables failure detection and identification (short circuit or sensor disconnection/ missing).
Symptoms
Reason
Operation
Display doesn't work.
Power supply failure.
Check the mains and the main fuses.
$IFDLUIF85UFNQFSBUVSFDVUPò
Replace the control panel.
Display shows flow failure
The flow value is „0” or is to low.
(below value of 12 l/min)
Heating is blocked.
Air lock in the heating system, solve the problem.
Deaerate the pump and the heating system.
Circulating pump is blocked.
Circulating pump is blocked. Make a manual pump
run. Use the screw to rotate the rotor.
Replace pump.
Flow sensor failure.
Replace flow sensor.
The supply temperature is too low.
Heating box failure.
Check or replace heating box.
"Faults” display view shows possible failures:
flow failure, outdoor/room temperature
sensor failure, inlet /outlet
boiler sensor failure. The controller enables
failure detection and identification
(short circuit or sensor disconnection/
missing).
Sensor failure
a) „Tzew-brak” or „ Tpok-brak”
The sensor is not reporting.
Check connection between controller and sensor.
Replace temperature sensor
b) „Tzew zwarcie” or „Tpok zwarcie”
Short circuit on the connection between
controller and sensor..
Check connection between controller and sensor.
The sensor is inversely connected.
Check the polarity of the sensor.
Failure of return or supply temperature
sensor.
Sensors failure.
$IFDLUIFTFOTPSSFTJTUBODF LȰBU¡$JG
damaged, replace the sensor. If the sensors are OK,
replace the control panel
PSK.M2.
Summary of Contents for ECKO.TM
Page 1: ...1 KOSPEL S A KOSZALIN ul Olchowa 1 SERVICE MANUAL EKCO T ECKO TM 17 11 2020 ...
Page 5: ...5 Pic 1b EKCO TM boiler 5 01216 19 01220 23 00035 32 6 01217 ...
Page 7: ...7 Pic 2bConstruction of the boiler EKCO TM ...
Page 26: ...Service manual EKCO T EKCO TM 26 14 2 Pump Wilo Yonos Para alarm status Tab 7 Alarm status ...