PL-090B_f.
27
If there are no defined time frames, then after
selecting „new” the time frame 00:00am to
23:59pm will be set , which should be edited in
accordance with user’s needs.
CH program No3
CH program No3
End
End
1 0:00 - 23:59
CH program No1
CH program No1
1 6:00 - 9:15
1 6:00 - 9:15
2 15:20 - 22:15
2 15:20 - 22:15
End
End
The daily program will be saved to the boiler’s
settings by pressing the command „END”.
Turbo mode
If the facility is cold and it is necessary to heat it up quickly, there is a possibility to
turn on the TURBO function. This function, when conditions to turn on the heating are
fulfilled, starts central heating installation with maximum parameters and continues until
required temperature is reached in a room. This function can start automatically when
room’s temperature falls down by the set value of Tr hysteresis. Automatic work is set
in menu
[Configuration > Aut. turbo mode.]
Selection of „DHW cylinder- NO” will result
in switching off hot water heating priority for the time of using Turbo function. In fast
modes menu it is possible to turn on this function manually (without hot water heating
up priority), in condition that the room’s temperature is lower than the programmed one.
Tr sensor is required to turn on the Turbo function.
Building anti-frost protection
Function’s activation
[Configuration > Central heating > Frost protection > Yes].
The frost protection function does not allow the building to cool down drastically. The
protection program starts the CH process if the following conditions are met:
- the boiler is in standstill mode or DHW mode,
- the outside temperature drops below 2°C. In case of failure of the Tos sensor, this
condition will always be met,
- the room temperature drops below 5°C. In case of failure of the Tr sensor, the frost
protection program will not turn heating on.
Depending on the type of regulation, the temperature setting of the heating medium will be
set accordingly to the calculations for the heating curve or manual setting. If the outside
temperature rises to at least 3°C or the room temperature rises to at least 6°C, the CH will
be switched off. The building protection function is inactive when controlling the boiler with
an external room controller connected to the RT entry.