3-38
3-3-13
4-point relay output module: J-04TRS
Relay life (ON→OFF 1 cycle)
Derating
*1 SPDT = Single pole double throw: Two pole contact, and both contacts are on. Single-Pole Double-Throw
I t e m
Output specification
Number of output
Four points
Number of occupied output
Eight points
Common
4 (1 point/common)
Rated output voltage
DC 24 V/AC 240 V
Operating voltage
Max. DC 30 V max. AC 264 V
Output type
Relay format C(SPDT)*1
AC frequency
47
~
63 Hz
Maximum output current
(resistance load)
7 A (point)/7 A (common)
Maximum leakage current
0.1 mA(AC 264 V)
Maximum rush current
12 A
Minimum load current
100 mA(DC 5 V)
Required current at main
power supply side
Max. 100 mA
Responses
times
OFF ON
Up to 15 ms
On and off
Up to 15 ms
Fuse
None
Loading condition
Life
DC 30 V, 7 A resistive loads
100,000 cycle or more
AC250 V, 7 A resistive load
100,000 cycle or more
AC250 V, 4.9 A inductive load
90,000 cycle or more
AC250 V, 2.9 A inductive load
100,000 cycle or more
C0
NC0
NO0
C1
NC1
NO1
C2
NC2
NO2
C3
NC3
NO3
NC
DC24V
AC240V
NC
NC
DC24V
AC240V
NC
NC
DC24V
AC240V
NC
NC
DC24V
AC240V
NC
出
力
点
数
周囲温度(℃)
0
10
20
30
40
50
60
0
1
2
3
4
55
5 A/pt.
7 A/pt.
DC 24 V
AC240 V
DC 24 V
AC240 V
DC 24 V
AC240 V
DC 24 V
AC240 V
L
NC
COM
DC24 V
AC240 V
Internal Module Circuitry
L
NO
No
of
output
points
Peripheral temperature (
℃
)
Summary of Contents for Kostac SJ-Ether Series
Page 1: ...English version of the KOSTAC SJ Ether series user s manual SJ ETHER USER M...
Page 12: ......
Page 13: ...1...
Page 14: ......
Page 88: ......
Page 89: ......
Page 113: ...3 24 Note Refer to 6 3 3 Module Assembly for connections and locks between modules...
Page 153: ......
Page 156: ...flashing OFF Not sent H W RX Green flashing Receiving H W OFF Not received H W...
Page 161: ...4 8...
Page 221: ......
Page 310: ...Chapter 7 Maintenance...
Page 311: ......