3-40
*1 SPST = Single pole single throw: When one pole contact is ON at the two pole contact. Single -Pole Single-Throw
Relay life (ON→OFF 1 cycle)
Derating
I t e m
Output specification
Number of output
Four points
Number of occupied output
Eight points
Common
1 (4 points/common)
Rated output voltage
DC 24 V/AC 240 V
Operating voltage
Max. DC 30 V max. AC 264 V
Output type
Relay formatA (SPST)*1
AC frequency
47
~
63 Hz
Max. output current
1 A (point)/4 A (common)
Maximum leakage current
0.1 mA(AC 264 V)
Maximum rush current
3 A(10ms)
Minimum load current
5 mA(DC 5 V)
Responses
times
OFF ON
Up to 15 ms
On and off
Up to 15 ms
Fuse
None
I t e m
Specification
Required current at main
power supply side
Max. 80 mA
Loading condition
Life
DC30V, 1A resistive loading
300,000 cycle or more
DC30V, 1A inductive loading
50,000 cycle or more
AC250V, 1A resistive loading
300,000 cycle or more
AC250V, 1A inductive loading
20,000 cycle or more
0
10
20
30
40
50
60
0
1
2
3
4
出
力
点
数
周囲温度(℃)
55
L
OUTPUT
COM
DC24V
AC240V
Internal Module Circuitry
No
of
output
points
Peripheral temperature (
℃
)
Summary of Contents for Kostac SJ-Ether Series
Page 1: ...English version of the KOSTAC SJ Ether series user s manual SJ ETHER USER M...
Page 12: ......
Page 13: ...1...
Page 14: ......
Page 88: ......
Page 89: ......
Page 113: ...3 24 Note Refer to 6 3 3 Module Assembly for connections and locks between modules...
Page 153: ......
Page 156: ...flashing OFF Not sent H W RX Green flashing Receiving H W OFF Not received H W...
Page 161: ...4 8...
Page 221: ......
Page 310: ...Chapter 7 Maintenance...
Page 311: ......