4-4
Fixed serial communication mode
The protocol in fixed serial communication mode is shown below.
Item
Performance
Remarks
Signaling
levels
RS-232C compliant
Transmission
rate
9600 bps fixation
Transmission
distance
Within the 10 m
Connecting Modular 6-pin connector (RJ-12), non-insulated
Protocol
CCM2
DirectNET
Programmer
only (K)
Non-procedural
communication
MODBUS/RTU
M-NET
Data format
HEX
ASCII
HEX
Not supported
HEX
Not supported
Data length
8 bits
←
8 bits
Stop
1 bit
←
←
Parity
Odd/even/none
←
←
Area code
1
~
90
←
1
~
247
※
300/600 per 1200 bps, 7-bit data length and non-parity combinations are not supported
General-purpose serial communication mode
The following protocols are used in the general-purpose serial communication mode.
Item
Performance
Remarks
Signaling
levels
RS-232C compliant
Transmission
rate
2400/4800/9600/19200/38400
Special register setting
Transmission
distance
Within the 10 m
Connecting Modular 6-pin connector (RJ-12), non-insulated
Protocol
CCM2
DirectNET
Programmer
only (K)
Non-procedural
communication
MODBUS/RTU
M-NET
The automatic switching function at
the time of reception is not
supported
by
non-procedural
communication.
Data format
HEX
ASCII
HEX
ASCII
HEX
Not supported
Data length
8 bits
←
7,8 bits
8 bits
Stop
1 bit
←
1,2 bits
←
Parity
Odd/even/none
←
←
←
Area code
1
~
90
←
61
、
62
、
6B
70
1
~
247
※
300/600 per 1200 bps, 7-bit data length and non-parity combinations are not supported
Summary of Contents for Kostac SJ-Ether Series
Page 1: ...English version of the KOSTAC SJ Ether series user s manual SJ ETHER USER M...
Page 12: ......
Page 13: ...1...
Page 14: ......
Page 88: ......
Page 89: ......
Page 113: ...3 24 Note Refer to 6 3 3 Module Assembly for connections and locks between modules...
Page 153: ......
Page 156: ...flashing OFF Not sent H W RX Green flashing Receiving H W OFF Not received H W...
Page 161: ...4 8...
Page 221: ......
Page 310: ...Chapter 7 Maintenance...
Page 311: ......