For each flag when using a general purpose communication port
Port2 Instructions for use
Specifying the port when using the WX/RX command
When transmitting and receiving data from port 2, set the following settings.
LDS KF1: The other station number = BCD2 digit send/receive port number is specified by F1.
LDS K0nnn: Number of read/write bytes
LDR O****...
RX/WX m xxxx •••••••••••••••••••••••••••••••••••••••••••••Counterparty's read/write start address
Port specification when MWX/MRX instruction is used
When sending and receiving Modbus from port 2, set the following settings.
Port number K2
When Port2 is used: Communication flag SP116
Communication error flag
SP117
Port3 Instructions for use
Specifying the port when using the EWX/ERX command (Fixed. Refer to Chapter 8 Appendix for other settings).
When Port3 is used: Available flag
SP200
Communication error plug SP201
※
If the setting completion code of the communication port is always written, communication may be impossible.
Write the setting completion code within one scan.