4-16
4-2-2
DirectNET
The SJ-Ether programmer communication port (Port1) and the general-purpose communication port (Port2) can be connected
to the communication master or the master/slave PLC to perform data communication. This communication is called
DirectNET, and all protocols (communication procedures) are common to all Koyo’s PLC.
(1)
DirectNET function
The DirectNET function of the SJ-Ether general-purpose communication port enables reading and writing of the following
data.
・
Reading timer elapsed value and counter count value
・
Read/Write Data Register
・
Read/write function memory (bits) such as I/O, internal relay, stage, etc.
(2)
Communication setting by register
Register number
Item
Setting range
Port 1
Port 2
Bit
R756
R7656
Bit0-6
Area code
1
~
90
R756
R7656
Bit7
Transmission mode
HEX/ASCII
R756
R7656
Bit14-15
Parity
None: NONE/Odd: ODD/even: EVEN
R756
R7656
Bit8-10
Transmission rate (bps)
2400/4800/9600/19.2k/38.4 k
R756
R7656
Bit13
Stop bit
1/2
R755
R7655
Bit8-11
Timeout period (ms)
800/960/1200/1600/4000/8000/16000/40000
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
CCM2/CCM3
局番設定(スレーブ局)
通信速度
1
*
*
*
0
0
0
0
0
0
*
*
*
*
*
*
ストップビット
00=
無し
01=
未定義
10=
奇数
11=
偶数
0=1
ビット
1=2
ビット
パリティ
伝送モード:
HEX/ASC
モード(
N
のみ)
3
:
2400
bps
R756,R7656
K/N:01
h~
5A
h(
1
~
90
)
4
:
4800
bps
5
:
9600
bps
6
:
19200
bps
7
:
38400
bps
485
2
線式フラグ
1
:
2
線式(
RS-485
、半二重)
未使用
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
RTS OFF Delay
0= 0ms
0
*
*
0
0
0
0
0
0
*
*
*
1
*
*
*
通信プロトコル設定
1= 2ms 2= 5ms 3= 10ms
4= 20ms 5= 50ms 6= 100ms 7= 200ms
08
:
M-NET
10
:無手順
20
:
MODBUS
40
:
CCM/DirectNET
80:K
シーケンス
タイムアウト倍率(基準時間
:K/N
=
800
ms)
0
:
×1
1
:
×1.2
2
:
×1.5
3
:
×2
4:
×5
5
:
×10
6
:
×20
7: ×50
応答遅延時間
0= 0ms 1= 2ms 2= 5ms 3= 10ms
4= 20ms 5= 50ms 6= 100ms 7= 200ms
R755,R7655
Response delay time
Communication protocol setting
10: No procedure 80: K sequence
Timeout multiplication(Standard time: K/N=800ms)
CCM2/3 area number setting (slave)
Transmission mode: HEX/ASC mode(only N)
Communication speed
2 wire type flag
1:2 wires type(RS-485, half-duplex)
Unused
Stop bit
0=1bit 1=2bit
Parity
00=None 01=Undefined 10=Odd 11=Even
Summary of Contents for Kostac SJ-Ether Series
Page 1: ...English version of the KOSTAC SJ Ether series user s manual SJ ETHER USER M...
Page 12: ......
Page 13: ...1...
Page 14: ......
Page 88: ......
Page 89: ......
Page 113: ...3 24 Note Refer to 6 3 3 Module Assembly for connections and locks between modules...
Page 153: ......
Page 156: ...flashing OFF Not sent H W RX Green flashing Receiving H W OFF Not received H W...
Page 161: ...4 8...
Page 221: ......
Page 310: ...Chapter 7 Maintenance...
Page 311: ......