4-3-3
CC-Link IEF Basic slave function
The following shows the CC-Link IEF Basic slave function.
Item
Contents
Station type
Slave station
SLMP commands
NodeSearch: Response
IPAddressSet: Not supported
Occupied station number
1 to 4 stations
However, the setting of occupied stations on the CC Link IE Field Network Basic ne
twork shall be in accordance with the specifications of the master device.
Cyclic data
RY
64 bits (8 byte) per station (capable of occupying more than one station)
RX
64 bits (8 byte) per station (capable of occupying more than one station)
RWw
32 word per station (capable of occupying multiple stations)
RWr
32 word per station (capable of occupying multiple stations)
IP address setting
The setting of communication port 3 (general-purpose Ethernet communication port) is enabled for the IP address.
Set the set value to the same network address as the master station.
When using the CC-Link IEF Basic function, set the value to the same subnet mask as the master station.
Be sure to set the subnet mask to "255.255.255.0".
For example:
Setting
Master station
Slave station
IP address
192.168.0.100
192.168.0.***
(192.168.0.1
~
192.168.0.254)
Can be set within the range
Subnet mask
255.255.255.0
255.255.255.0
(The value of the same subnet mask as the mast
er station)
CC Link IEF Basic communication method
There are three types of CC-Link IEF Basic communication methods for SJ-Ether. Each function is defined below.
#
Function name
CC-Link IEF Basic
Communications func
tion
Data-link
Special relay
Special registe
r
Renewal
SLMP
Command fun
ction
1
Communication disabled
Invalid
Invalid
None
Invalid
2
No data link (communication is en
abled)
Valid
Invalid
Yes
Valid
3
Data link (communication enabled)
Valid
Valid
Yes
Valid
Communication disabled
CC-Link IEF Basic communication is disabled. Data link processing is disabled. The SLMP commands feature is
enabled.
Data reading and writing with the CC Link IEF Basic master station is not possible on the ladder program.
Summary of Contents for Kostac SJ-Ether Series
Page 1: ...English version of the KOSTAC SJ Ether series user s manual SJ ETHER USER M...
Page 12: ......
Page 13: ...1...
Page 14: ......
Page 88: ......
Page 89: ......
Page 113: ...3 24 Note Refer to 6 3 3 Module Assembly for connections and locks between modules...
Page 153: ......
Page 156: ...flashing OFF Not sent H W RX Green flashing Receiving H W OFF Not received H W...
Page 161: ...4 8...
Page 221: ......
Page 310: ...Chapter 7 Maintenance...
Page 311: ......