4-52
4-3-5
Error record register/status notification relay/reset request/queue request
The following error record registers and special relays announce the communication status of the CC-Link IEF Basic sl
ave function. In addition, the reset/solution queue request relay accepts requests only when the rising edge is detected.
Name
Special relay
Contents
Master station status
SP250
Stores the operation status of the main function of the master station.
0: Master station is stopped.
1: Master station running
Parameter setting completion fla
g
SP251
Notifies that the parameters for CC-Link IEF Basic are set correctly.
OFF when an error occurs or when the function is disabled.
0:Parameter error or function disabled
1:Parameter is normal (function is enabled)
Queued state
SP252
This field is set to the CC Link IEF Basic communication status.
0:Network unwinding (disconnecting)
1: Network duplex
Error occurrence flag
SP253
This switch is turned on when an error related to CC Link IEF Basic
communication is detected.
This bit is turned ON when there is a bit in the ON state at any one
of the error cause registers when an error occurs.
0:No abnormality (normal)
1:Abnormal
Desorption counter
R7706
Counts the number of times the slave station is disconnected.
Queue counter
R7707
Counts the number of resolutions of slave stations.
When the slave station is disconnected, the number of dissociation col
umns is also counted.
Abnormal factors
R7730
Stores the error cause of CC Link IEF Basic communication.
When the alarm is reset, it is turned off automatically.
Generic switch
R7731
This is a general switching function for the CC Link IEF Basic com
munication function. Each bit is assigned a function.
The value is cleared to 0 when the power is turned on.
Bit0: Uncolumns Request
Bit1 – bit14: Not Used
Bit15: Communication reset request
Master station
Calendar (seconds)
R7732
The information is updated only while you are participating in the net
work.
0
~
59[BCD]
Master station
Calendar (minutes)
R7733
The information is updated only while you are participating in the net
work.
0
~
59[BCD]
Master station
Calendar (Hour)
R7734
The information is updated only while you are participating in the net
work.
0 to 23 (24h notation) [BCD]
Master station
Calendar (days)
R7735
The information is updated only while you are participating in the net
work.
1
~
31[BCD]
Master station
Calendar (month)
R7736
The information is updated only while you are participating in the net
work.
1
~
12[BCD]
Master station
Calendar (year)
R7737
The information is updated only while you are participating in the net
work.
00
~
99[BCD]
Summary of Contents for Kostac SJ-Ether Series
Page 1: ...English version of the KOSTAC SJ Ether series user s manual SJ ETHER USER M...
Page 12: ......
Page 13: ...1...
Page 14: ......
Page 88: ......
Page 89: ......
Page 113: ...3 24 Note Refer to 6 3 3 Module Assembly for connections and locks between modules...
Page 153: ......
Page 156: ...flashing OFF Not sent H W RX Green flashing Receiving H W OFF Not received H W...
Page 161: ...4 8...
Page 221: ......
Page 310: ...Chapter 7 Maintenance...
Page 311: ......