5-2-8
Lamp/soak table address (a34)
In each loop, you can configure the target value (set point) using the built-in lamp/soak data. Use this lamp/soak data to create
an SP value. To use the lamp/soak function, you must have the appropriate value in the 32-word area. The KPP dialog box
facilitates this operation.
Address +34 of the control table specifies the start address of the lamp/soak table. This can be assigned anywhere in user
memory. You do not need to be adjacent to the control parameter table as shown on the left. Each lamp/soak table requires 32
words regardless of the number of steps set.
Lamp/soak table parameters are defined in the table below.
Address
offset
Step
Number
Description
Address
offset
Step
Number
Description
+ 00
1
Lamp SP value
+ 20
9
Lamp SP value
+ 01
1
Lamp slope
+ 21
9
Lamp slope
+ 02
2
Soak time
+ 22
10
Soak time
+ 03
2
Allowable deviation
+ 23
10
Allowable deviation
+ 04
3
Lamp SP value
+ 24
11
Lamp SP value
+ 05
3
Lamp slope
+ 25
11
Lamp slope
+ 06
4
Soak time
+ 26
12
Soak time
+ 07
4
Allowable deviation
+ 27
12
Allowable deviation
+ 10
5
Lamp SP value
+ 30
13
Lamp SP value
+ 11
5
Lamp slope
+ 31
13
Lamp slope
+ 12
6
Soak time
+ 32
14
Soak time
+ 13
6
Allowable deviation
+ 33
14
Allowable deviation
+ 14
7
Lamp SP value
+ 34
15
Lamp SP value
+ 15
7
Lamp slope
+ 35
15
Lamp slope
+ 16
8
Soak time
+ 36
16
Soak time
+ 17
8
Allowable deviation
+ 37
16
Allowable deviation
Note: DirectSOFT4 and DirectSOFT5 are not supported.
Be sure to use KPP Ver1. 5.0.0 or higher.
5-2-9
Lamp/soak table setting error flag (a35)
The definition of each bit of the lamp/soak table setting error flag (a 35) is listed in the table below.
Bites
R/S error flag bit description
Read/write
Bit = 0
Bit = 1
0
Register area start address is out of range (lower)
Reading
–
Error
1
Start address of register area is out of range (higher)
Reading
–
Error
2–3
Scheduled
–
–
–
4
Start address of the register area specifies the system
parameters
Reading
–
Error
5–15
Scheduled
–
–
–
R 200 0
R 203 7
R 300 0
レジスタ空間
ユーザデータ
ループ
No.1
32
ワード
ループ
No.2
32
ワード
ランプ/ソーク
No.1
32
ワード
R2034=3000
(
8
進表記)
R/S
テーブルへのポインタ
Register area
User data
Loop No.1
32 words
Loop No.2
32 words
Lamp/Soak No.1
32 words
R2034=3000 (Octal)
Pointer to R/S table
Summary of Contents for Kostac SJ-Ether Series
Page 1: ...English version of the KOSTAC SJ Ether series user s manual SJ ETHER USER M...
Page 12: ......
Page 13: ...1...
Page 14: ......
Page 88: ......
Page 89: ......
Page 113: ...3 24 Note Refer to 6 3 3 Module Assembly for connections and locks between modules...
Page 153: ......
Page 156: ...flashing OFF Not sent H W RX Green flashing Receiving H W OFF Not received H W...
Page 161: ...4 8...
Page 221: ......
Page 310: ...Chapter 7 Maintenance...
Page 311: ......