6-2-3
Selection of power supply module
There are two types of power supply modules with output current. Calculate and select the current consumption as shown below.
Refer to 3-2 Power Module for details of the power module.
Calculation of current consumption
The SJ Ether PLC provides the power supply DC24 V from
the power supply module to the CPU module and uses the
transformed DC3. 3 V in the CPU module as the internal
power supply. Therefore, the sum of the current consumed by
the SJ-Ether PLC and peripheral devices, including the
extended I/O modules, must be less than or equal to the output
current capacity of the power supply modules. The table
below shows the maximum current consumed (required
current at the main power supply (DC24 V) side) of the
respective modules.
Checking items
Power supply module output current > CPU + extended I/O
total current consumption of peripheral equipment
(1)
CPU current consumption
Type
Model number
Discrete
Analog
Maximum current
※
1
(mA)
Input
Output
AD
DA
Ba
sic
SJ-11DD1E-D
Eight DCs
Six DC sinks
―
―
110
SJ-11DD2E-D
Eight DCs
Six DC sources
―
―
110
SJ-11DRE-D
Eight DCs
Six relays
―
―
140
SJ-11DD1EP-D
Eight DCs
Six DC sinks
―
―
110
SJ-11DD2EP-D
Eight DCs
Six DC sources
―
―
110
SJ-11DREP-D
Eight DCs
Six relays
―
―
140
An
alo
g
SJ-12DD1E-D
Four DCs
Four DC sinks
Two
points
Two
points
140
SJ-12DD2E-D
Four DCs
Four DC sources
Two
points
Two
points
140
SJ-12DRE-D
Four DCs
Four relays
Two
points
Two
points
160
SJ-12DD1EP-D
Four DCs
Four DC sinks
Two
points
Two
points
140
SJ-12DD2EP-D
Four DCs
Four DC sources
Two
points
Two
points
140
SJ-12DREP-D
Four DCs
Four relays
Two
points
Two
points
160
※
1: When the communication port is not powered
Model number
Output current(DC24 V)
C0-01AC
1300 mA
電源モジュールの選択
CPU、各拡張I/Oモジュール
最大消費電流の総和
J-00AC選択
500 mA≧消費電流の総和
J-01AC選択
N
Y
Selection of power
supply module
CPU, each extended I/O module
Total of maximum consumption of
electrical current
500 mA
≧
Total of consuming
current
J-00AC selection
J-01AC selection
Summary of Contents for Kostac SJ-Ether Series
Page 1: ...English version of the KOSTAC SJ Ether series user s manual SJ ETHER USER M...
Page 12: ......
Page 13: ...1...
Page 14: ......
Page 88: ......
Page 89: ......
Page 113: ...3 24 Note Refer to 6 3 3 Module Assembly for connections and locks between modules...
Page 153: ......
Page 156: ...flashing OFF Not sent H W RX Green flashing Receiving H W OFF Not received H W...
Page 161: ...4 8...
Page 221: ......
Page 310: ...Chapter 7 Maintenance...
Page 311: ......