Chapter 2 Systems specification
2-24
Number
N a m e
C o n t e n t s
Initial value
R7616
Ch3 timer interrupt
Setting time
Setting range 1 to 9999 ms (BCD), 0: Interrupt not
used
Interrupt number: ILBL O12
0
R7617
Ch4 timer interrupt
Setting time
Setting range 1 to 9999 ms (BCD), 0: Interrupt not
used
Interrupt number: ILBL O13
0
R7620-R7627
For S-10D
Operation display panel: Register area used by S-01D
None
R7630-R7631
Preliminary
0000
R7632
Password setting
Bit15: Password reading disabled
0
R7633
For CPU special function
setting
Signed operations of bit15:16 bit binary arithmetic
instructions
Bit14: Preliminary
Bit13: RUN mode at startup (ON: RUN mode)
Bit12: Battery present (ON: Battery present)
Bit11-0: Preliminary
0000
R7634-R7637
Preliminary
0000
R7640
For PID operation
PID start table setting top register specification
0
R7641
For PID operation
Loop count setting
0
R7642
For PID operation
Error flag storage
0
R7643-R7645
Prohibition of use
0000
R7646
MODBUS/RTU
Timeout setting (Port2)
MODBUS/RTU
communication:
Character-to-character timeout setting
0000
R7647
MODBUS/RTU
Timeout setting (Port1)
MODBUS/RTU
communication:
Character-to-character timeout setting
0000
R7650
Non-procedural
communication:
Setting completed code
General-purpose
communication
port
(Port2)
No-procedure serial communication: Set [A55A]
when setting is completed.
0
R7651
Non-procedural
communication:
Format set
General-purpose
communication
port
(Port2)
No-procedure serial communication: Data format
setting
E
R7652
Non-procedural
communication:
Configuring transmit and
receive modes
General-purpose
communication
port
(Port2)
Non-procedure serial communication: 61/62/6B/70 is
set.
70
R7653
Non-procedural
communication:
Terminate code
General-purpose
communication
port
(Port2)
No-procedure serial communication: Set the reception
completion code.
0
R7654
Non-procedural
communication:
Storage of received data
General-purpose
communication
port
(Port2)
Non-procedure
serial
communication:
Register
number (OCT) completed
400
R7655
Communications protocol
General-purpose
communication
port
(Port2):
Communication protocol selection
00E0
R7656
Transmission
rate,
response delay
General-purpose communication port (Port2): Setting
of transmission rate, etc.
8D01
R7657
Storage of communication
protocol setup completion
code
General-purpose communication port (Port2): Set the
setting completion code.
0A00
Summary of Contents for Kostac SJ-Ether Series
Page 1: ...English version of the KOSTAC SJ Ether series user s manual SJ ETHER USER M...
Page 12: ......
Page 13: ...1...
Page 14: ......
Page 88: ......
Page 89: ......
Page 113: ...3 24 Note Refer to 6 3 3 Module Assembly for connections and locks between modules...
Page 153: ......
Page 156: ...flashing OFF Not sent H W RX Green flashing Receiving H W OFF Not received H W...
Page 161: ...4 8...
Page 221: ......
Page 310: ...Chapter 7 Maintenance...
Page 311: ......