2.3 Input Specifications
Number of Input Channels 4
Range
0-10V
Resolution
12 bit
Input Impedance
1M
Ω
±5%
PLC Update Rate
4 input channels per scan
Conversion Method
Successive approximation
Isolation Type
None
Maximum Error
±0.3% of full scale
2.4 Output Specifications
Number of Output Channels 2
Range
0-10V
Resolution
12 bit
Load Impedance
Minimum 2000
Ω
PLC Update Rate
2 output channels per scan
Isolation Type
None
Maximum Error
±1.0% of full scale
2.5 Wiring
2.5.1 Wiring Guidelines
Your company may have guidelines for wiring and cable installation. If so, check
the guidelines before beginning the installation. Here are some general things to
consider:
1
、Use the shortest wiring route whenever possible.
2、Wire strictly according to the label on the terminal, do not mix the wires of different
channels to avoid interference.
3 、 Do not run the signal wiring next to large motors, high current switches, or
transformers. This may cause noise problems.
4、Users can choose the wiring method that suits them, but all wiring must meet the safety
requirements to avoid accidental danger.