background image

 

 

 

 

2.5.2  Wiring Diagram 

 
 

Note: 
1、Do not mix the wires of different channels 
to avoid interference. 
2、Connect the unused ADn to SG to avoid 
interference. 
3、All SG terminals are internally 
connected. 
 
ADn represents input channels AD1,AD2,
AD3,and AD4. 
 
 
 
 
 
 
 
 
 

 

2.6  Registers Used by NK1-B4AD2DA-2 

 

The use of the optional function board does not require any settings, as long as 

the unit is installed on the NK1 series PLC (for specific installation methods, please 
refer to the chapter about the optional function board in the "NK1 User Manual"), you 
can read or write the relevant registers directly through the program to implement the 
analog input and output functions. The registers used by this option function board 
are shown in the following table. 
 

NK1-B4AD2DA-2(0-10V) 

Channel 

Register 

Analog Input 

AD1 

R37420 

AD2 

R37421 

AD3 

R37422 

AD4 

R37423 

Analog Output 

DA1 

R37424 

DA2 

R37425 

 
Note: After the optional function board is installed on the NK1 series PLC, the registers 

listed in the table above are provided for the exclusive use of the optional 
function board. Please do not use these registers for other purposes in the user 
system. 

Summary of Contents for NK1 Series

Page 1: ...Value Technology NK1 Series PLC Manual NK1 B4AD2DA 2 Function Board 1st Edition KOYO ELECTRONICS WUXI CO LTD...

Page 2: ...uction 2 2 2 General Specifications 2 2 3 Input Specifications 3 2 4 Output Specifications 3 2 5 Wiring 3 2 5 1 Wiring Guidelines 3 2 5 2 Wiring Diagram 4 2 6 Registers Used by NK1 B4AD2DA 2 4 2 6 1 A...

Page 3: ...the factory If you need backup lithium battery please purchase separately Model is RB 50 For the installation and removal of the option function board please refer to the relevant chapter in the NK1...

Page 4: ...n board are as follows The resolution of analog input is 12 bit The resolution of analog output is 12 bit No external power supply required With OK indicator green it will be on during normal work 2 2...

Page 5: ...full scale 2 5 Wiring 2 5 1 Wiring Guidelines Your company may have guidelines for wiring and cable installation If so check the guidelines before beginning the installation Here are some general thi...

Page 6: ...chapter about the optional function board in the NK1 User Manual you can read or write the relevant registers directly through the program to implement the analog input and output functions The regist...

Page 7: ...apply voltage signals other than 0 10V to the input terminal of this function board otherwise the option function board and NK1 series PLC main unit may be damaged 2 6 2 Analog Output Registers This o...

Page 8: ...2 6 3 Module Resolution 0 3FF H 7FF H BFF H FFF H 0 1023 2047 3071 4095 0V 2 5V 5V 7 5V 10V Analog value Digital value...

Page 9: ...yo ELECTRONICS WUXI CO LTD Add 21st Floor Building 1 No 599 Jianzhuxi Road Binhu District Wuxi Jiangsu P R China Pc 214072 Tel 0510 85167888 Fax 0510 85161393 http www koyoele com cn KEW M2523A 2 2020...