SECTION 6
VENTING
#LXL-22-L
R.1 4 . 2 0 . 2022
25
HUSSONG MFG. CO., INC.
KOZY HEAT FIREPLACES
6.4.2
Combination Venting
Natural Gas and Propane Installations
IMPORTANT: Horizontal vent sections require 1/4” (6mm) of rise for
every 12” (305mm) of travel.
Vent termination must be within the shaded area in
FIGURE 6.3
.
25’ (7.6m) maximum vertical rise + 25’ (7.6m) maximum horizontal run
= 50’ (15.2m) of total length
Combination Venting Natural
•
Maximum of (5) 90° elbows. For each additional 90° elbow
used after the first elbow, 3’ (914mm) must be subtracted from
maximum venting allowed.
•
(2) 45° degree elbows may be used in place of (1) 90° elbow.
For each 45° elbow used, 18” (457mm) must be subtracted from
maximum venting allowed.
FIGURE 6.3
Combination Venting