1.  Turn off all electrical power to fireplace.  

 NOTE:  When fireplace is initially lit, condensation will appear  
                on the glass; this is normal in all gas fireplaces and will    

disappear after several minutes. 

LIGHTING AND SHUTDOWN (cont.) 

  

3.  Wait five (5) minutes to allow any gas that may have accumulated 

inside firebox to escape. If you then smell gas, 

STOP! 

  Follow safety 

information on front cover and on previous page of this  

installation manual.  If you don‟t smell gas, go to next step.

 

 

LIGHTING  

5 MINUTES 

CAUTION:  If fireplace will not operate, follow instructions  
 

    TURNING OFF GAS TO FIREPLACE and call  

 

    your service technician or the gas supplier. 

ATTENTION: This fireplace is equipped with an ignition device 
 

         which automatically lights the pilot.  

 

         DO NOT light the pilot by hand. 

2.  Press hand held remote 

MODE

 button to 

OFF

4.  Turn ON all electrical power to fireplace. 

5.  Press hand held remote 

MODE

 button to 

ON

STOP!  Read safety information on previous page and front                       

cover of this manual before continuing. 

TURNING OFF GAS TO FIREPLACE 

1.  Press hand held remote 

MODE

 button to 

OFF

 
 

2.  Turn OFF all electrical power to fireplace if service is required. 

 
 

3.  Turn manual shut-off valve to 

OFF

Power OFF 

Power ON 

OFF 

ON 

Figure 28a 

Power OFF 

OFF 

Figure 28b 

Summary of Contents for MPS-34 Minneapolis XL

Page 1: ...Vehicles and Mobile Housing CSA Z240 4 Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance IF YOU SMELL GAS Do not light any appliance Do...

Page 2: ...on and reliability but customer safety as well We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat gas fireplace Jim Hussong Dudley Hu...

Page 3: ...Conversion Kit Instructions 12 13 GLASS FRAME ASSEMBLY SCREEN FRONT Glass Frame Assembly Screen Front Removal Installation 14 INSTALLATION Approved Venting 14 Combustion Air Venting Options 14 Air Du...

Page 4: ...keep toddlers young children and other at risk individuals out of the room and away from hot surfaces Clothing or other flammable material should not be place on or near the appliance Adequate access...

Page 5: ...Black firebox liner Glass Media Kit IPI control system with remote control Engineer designed burner system Automatic fan kit 1 75 CFM Light Kit Co linear vent system 3 combustion air 3 exhaust Innovat...

Page 6: ...8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print no less the one half inch 1 2 in...

Page 7: ...t Center FIREPLACE DIMENSIONS INCHES 23 5 8 34 28 3 16 16 3 8 24 1 2 7 1 4 1 3 8 10 1 4 6 1 8 MILLIMETERS 600 864 716 416 622 184 35 260 156 1 Fireplace insert 2 Air chute 3 Module panel assembly 4 Va...

Page 8: ...SPECIFICATIONS PAGE 7 MINIMUM CLEARANCES TO COMBUSTIBLES Figure 7a...

Page 9: ...Glass Media Kit 2 JXL 057T Glass Frame Assembly OCK A53L I MXL PSE LP Conversion Kit 816 CL1 Co Linear Air Duct 700 208 Remote Control 700 GLT Glass Latch Tool Vent System Part 816 CL For use with min...

Page 10: ...nside diameter Existing Chimney Height Minimum 10ft 3 05m Maximum 35ft 10 67m 1 Remove and discard existing chimney cap 2 Position one person at fireplace and another person at top of chimney Measure...

Page 11: ...s screen rails screen mesh and log grates may be removed from existing fireplace before installing this gas fireplace insert Any smoke shelves shields and baffles may be removed if attached by mechani...

Page 12: ...ith the requirements of the ANSI Z223 1 installation code NOTE A listed and Commonwealth of Massachusetts approved 12 13mm manual shut off valve and flexible gas connector included are connected to th...

Page 13: ...so now before installing into existing fireplace REPLACE BURNER ORIFICE 1 Remove burner secured with 2 screws 2 Remove existing orifice cap Replace with orifice cap included with kit making sure to ti...

Page 14: ...pressure Visually check pilot flame Flame should envelope top of flame sensor and extend onto burner far enough for prop er ignition To Adjust pilot Turn pilot adjustment screw clockwise to decrease...

Page 15: ...ith slots on insert set into position To remove Lift frame up and out of slots PAGE 14 Figure 14a INSTALLATION COMBUSTION AIR VENTING OPTIONS OPTION 1 FULL CONNECTION Combustion air intake pipe is run...

Page 16: ...sealant around inner edge at end of exhaust pipe without collar red marking and slide onto corresponding collar on termination cap collar with label Secure with 3 self tapping screws provided Apply ad...

Page 17: ...sen vent system OPTIONAL 816 CL kits Secure termination cap to existing chimney with 2 self tapping screws and anchor straps provided through pilot holes located at sides of termination cap 3 From ins...

Page 18: ...llar on air duct Slide combustion intake pipe over collar Secure with 3 self tapping screws provided To ensure an air tight seal apply additional sealant around joint 4 Slide insert into fireplace ope...

Page 19: ...ION Disconnect all electrical power from fireplace before performing this task NOTE To avoid damage and prolong the life of halogen bulbs never touch with bare hands Always use a soft cloth when handl...

Page 20: ...19a IMPORTANT THIS SYSTEM REQUIRES ELECTRICITY 110 V AND OR BATTERIES TO OPERATE USING BATTERY BACK UP WILL OPERATE BURNER ONLY FAN COMPONENTS WILL NOT FUNCTION ON BATTERY BACK UP POWER Light kit not...

Page 21: ...OR LOW LIMIT SCREW STEP MOTOR WIRE HARNESS MAIN VALVE INTERNAL SOLENOID CONNECTION PILOT INTERNAL SOLENOID CONNECTION PILOT ADJUSTMENT SCREW INLET PRESSURE SCREW OUTLET MANIFOLD PRESSURE SCREW IPI GAS...

Page 22: ...N OFF SWITCH LEARN BUTTON MAIN CONTROL MODULE VALVE STEP MOTOR TERMINAL COMMUNICATION LINK TO EXTENSION MODULE AC ADAPTOR CONNECTION EXTENSION MODULE COMMUNICATION LINK TO CONTROL MODULE POWER TO LIGH...

Page 23: ...CONTROL INFORMATION CHILD PROOF ICON LIGHT LEVEL FLAME HEIGHT FAN SPEED BATTERY LIFE ICON THERMOSTAT MODE ICON SET TEMPERATURE visible only in THERMO MODE MANUAL ON OFF ROOM TEMPERATURE CONTINUOUS PI...

Page 24: ...d may cause an explosion Disconnect 110V before servicing The IPI gas control system has the option of a continuous standing pilot feature This allows you to change from a spark to pilot system to a s...

Page 25: ...n on right side access panel A Velcro strip has been attached to help secure in place The Hand Held Remote operates on 2 1 5V AAA batteries We recommend always using ALKALINE batteries to extend batte...

Page 26: ...ain will turn fireplace OFF NOTE The MODE button operates in a series that will cycle from ON to THERMO to OFF FAN MODE This remote will operate the fan allowing for 6 different speed levels When the...

Page 27: ...ature The FLAME ON and THERMO icons will appear on the LCD screen By pressing UP or DOWN buttons a new set temperature may be attained SET Temperature will only appear when THERMOSTAT MODE is activate...

Page 28: ...P CHILDREN CLOTHING AND FURNITURE AWAY This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air WHAT TO DO IF YOU SME...

Page 29: ...not operate follow instructions TURNING OFF GAS TO FIREPLACE and call your service technician or the gas supplier ATTENTION This fireplace is equipped with an ignition device which automatically light...

Page 30: ...re Follow instructions below for proper testing procedures INLET PRESSURE TEST PRESSURE TESTING NOTE If inlet pressure reading is too high or too low contact the gas company Only a qualified gas servi...

Page 31: ...ot flame is actually present when valve is turned OFF if yes replace valve Replace pilot assembly Replace module SENSOR SAFETY Protection for Flame Sensor Error Code Four beeps every two seconds Descr...

Page 32: ...YOUR INSTALLATION NATURAL GAS LP PROPANE GAS 1 16 2 mm OPEN 5 8 16mm OPEN BURNER TUBE VENTURI ADJUSTMENT GUIDELINES VENTURI POSITION FLAME COLOR VENTURI ADJUSTMENT Closed too far Dark orange flame wit...

Page 33: ...d agency is required IF VENT AIR INTAKE SYSTEM IS DISASSEMBLED FOR ANY REASON RE INSTALL PER INSTRUCTIONS PROVIDED WITH INITIAL INSTALLATION The flow of combustion and ventilation air must not be obst...

Page 34: ...ing for a beep from receiver when ON is pressed on hand held remote If you do not hear a beep ensure main control module has learned the hand held remote See above Ensure black lead from pilot assembl...

Page 35: ...may take up to 3 hours for the temperature inside a packaged transmitter and several minutes for an unpackaged transmitter to equalize with room temperature FIREPLACE WILL NOT RESPOND IN THERMO MODE...

Page 36: ...Natural Gas Orifice 41 700 404 MXL 1 Minneapolis XL IPI Valve LP 700 253 LP Gas Orifice 53 700 200 Pilot Assembly Natural Gas OCK A41N I MXL PSE Natural Gas Conversion Kit 700 200 1 Pilot Assembly LP...

Page 37: ...PAGE 36 LIMITED WARRANTY...

Page 38: ...PAGE 37 LIFETIME WARRANTY...

Reviews: