background image

Pressure Surge Damper, 

Type RK-F10

Preliminary notes

Pressure surge dampers shall protect rooms,
facilities and ductwork against pressure 
blasts. Such pressure waves could be pro-
duced by chemical reactions, gas-explo-
sions or mechanical damages at pressure 
vessels. They can reach in about 100 milli-
seconds a positive pressure of approx. 0.45 
bar and their duration will take about 1 s. 
(see graphic).

Characteristics of pressure waves

Installation situation

Air flow and pressure loss

Application

In case of a requirement that single duct legs
or wall openings has to be open in normal 
operation and to be closed in a pressure wave 
resp. a pressure increasing situation, Krantz 
recommend to use of their pressure surge 
damper, type RK-F10.

According to the closing pressure an initial 
tension will be adjusted at an installed spring 
system. This initial tension ensures an open 
position of the damper regarding wind blasts 
and variation of pressure inside the duct sys-
tem. In open position and case of installation 
outside of outer walls the damper also fulfils 
the functions of a rain protection grille.

Pressure Surge Damper, Type RK-F10

July 2013

Page 2/6

info.filter@krantz.de

www.krantz.de

Krantz Filter Systems and Dampers

Reviews: