10. Consumables
Replacements for these pre-filter and HEPA filter elements should be procured from Krantz GmbH,
since only these filter elements have an inactivating, antiviral lining! The use of other filter
elements will void any warranty and Krantz cannot accept any liability for any damage that results!
Orders can be placed using the following contact details:
Krantz GmbH I Uersfeld 24 I 52072 Aachen
Phone: +49 (0) 0241 441- 0
10.1 Pre-filter Element
Pre-filter element, designed as a filter mat
Filter mat with patented inactivating
lining
Filter class ePM10, in accordance with ISO16890 (old M5, in accordance with EN779)
Dimensions W x H x D:
620 x 620 x ~20 [mm]
Initial pressure drop:
~ 20 [Pa), depending on the preselected volume flow
Recommended final
pressure difference:
250 [Pa]
Article name:
Pre-Filter, Krantz VIRUS
PROTECT
ID No.:
268_ePM10_antiviral
10.2 HEPA
Filter
Element
HEPA filter element in cassettes shape
Filter paper with a patented inactivating
lining
Filter class H14 in accordance with EN1822
Dimensions W x H x D:
610 x 610 x 170 [mm]
Frame:
Galvanized steel
Sealing compound:
Polyurethane
Spacers:
Aluminum
Seal:
Continuous seal, EPDM
Initial pressure drop:
~ 100 [Pa), depending on the preselected volume flow
Recommended final
pressure difference:
400 [Pa]
Article name:
HEPA Filter, Krantz VIRUS
PROTECT
ID No.:
268_H14_antiviral
Note:
A set of internal sound absorbing panels is supplied with each HEPA filter.
These panels have an inactivating lining and must be changed together with the pre-filter
element.