Agitator motor and blower should only be operated with steady or constant flow of electricity
between 110-120 volts.
Note:
When using extension cords, wire gauge size should not be less than input cord on unit and
not exceed 50' in length.
(See Voltage Drop Chart Below.)
Ex: A two-wire 20-ampere circuit using 12 AWG with a one-way distance of 25 feet will drop 1.98 volts;
120 volts - 1.98 volts = 118.02 volts as the load voltage.