__________________________________________________________________________________________
Kreyer – Picture guide to installation and start-up MCK and Chilly Max (page 10 of 18) v.07-2015
Attention:
Please check the pressure capacity of the unit pump. Please ensure that all
components in your water system are compatible with the maximum pump pressure. If necessary,
use pressure-reducer elements (e.g. bypass-valve) in your water system. Pump capacity and further
information are inside the instruction manual.
Step 15: When the pump pressure is correctly set adapted to your tank installation -
The integral pump inside the cooling unit would switch-off when all tank valves are closed and there
is temporarily no requirement for cooling/heating -> this needs to be adjusted.
While operating the unit take a screw driver, open the casing of the differential pressure switch and
adjust it corresponding to the description in the instruction manual. Afterwards close the casing of
the pressure switch and close all open cover panels of the unit.
The chiller is now successfully adjusted and ready for use!