background image

Tel:

 +44 (0)1274 657 088   

Fax:

 +44 (0)1274 657 087   

Web:

 www.cromptonlamps.com

Images are for information only. Phoebe LED shall not be held liable for improper operation of the luminaire 

in circumstances where procedures and specifications have not been followed correctly. Crompton Lamps Limited 2020

TESTING

24hrs Initial charge time required.

The emergency lighting must be inspected and tested regularly in accordance 

with local codes of practice:

note:

 for safety reasons tests should be carried out during daylight hours.

AFTER INSTALLATION

Allow 24 hours to ensure full battery charge and then interrupt the supply; the 

maximum duration time is 3 hours check that LEDs are still lighting.

FUNCTIONAL TEST (Short)

Monthly, interrupt mains for a short period and check LED lights.

DURATION TEST

Full duration test should be carried out annually, interrupt mains and check LED 

lights. LEDs will light and should last for a minimum 3 hours operation:

batteries must be replaced when they can no longer support 3 hour operation.

LED

STATUS

COMMENT

Green

Standby, system ok

Mains operation, battery charging

Off

Battery Operation

Emergency mode: 

Mains disconnected or Mains failure

INDICATOR LED

System status is shown locally by the indicator LED.

INSTALLATION MAINTENANCE RECORD

Month

TEST

Year 1

Year 2

Year 3

Year 4 

(Out of Warranty)

Signed

Date

Signed

Date

Signed

Date

Signed

Date

1

Short

2

Short

3

Short

4

Short

5

Short

6

Short

7

Short

8

Short

9

Short

10

Short

11

Short

12

Short

3 Hr

Installer

Installation Date

Installation Test Date

Reviews: