65
. 3
. 3
ONLY OPEN
for use in fan systems
. 4 . 4
OPEN partially
. 5 . 5
OPEN the door when it is in
closing phase (reverse action)
Note
. 5
is the default setting
6
.
3
Electric lock control
(electric lock) 24 V DC
6.3
Press and hold the SET button for about 6 se-
conds until the display shows 0.; then release
the button
- use the + button to select 6.; then shortly
press the SET button to select this function
- press the SET button again and the display
will show 6.0 (default)
- use the + button to select 6.3; then briefly
press the SET button to select this function
and display the parameters:
. 0 . 0
The electric lock control function
is disabled
. 1
. 1
The electric lock control function is enabled
1 sec. before opening the door, the electric lock
control voltage appears at the output, locking
the bolt (operation time 1.5 sec.)
After 1 sec. before the door is close, the electric
lock control voltage appears at the output,
locking the bolt (operation time 1.5 sec.)
Note
By default, the feature is disabled
SETTINGS OF FUNCTION PARAMETERS IN MENU