ELECTRICAL CONNECTIONS
26
H250
www.krohne.com
04/2009 - 4000269302 MA H250-R02
If the pointer vane enters the slot, an alarm is triggered. If the pointer vane lies outside the slot
sensor, a wire break also causes the alarm to be triggered.
The 3-wire limit switch does not have any wire break detection.
Current consumption in the position shown:
Switch contact definition
1
MIN contact
2
MAX contact
3
Pointer vane with switching vane
Definition MinMin - MaxMax
1
MIN 2 contact or MAX 1 contact
2
MIN 1 contact or MAX 2 contact
Contact
Type
Current
MIN 1
NAMUR
≤
1 mA
MIN 2
NAMUR
≤
1 mA
MAX 1
NAMUR
≥
3 mA
MAX 2
NAMUR
≥
3 mA