ELECTRICAL CONNECTIONS
4
37
H250
www.krohne.com
04/2009 - 4000269302 MA H250-R02
4.4.3 Switching outputs B1 and B2
The switching outputs are electrically isolated from each other and from the current output.
Switching outputs B1 and B2 can be electrically connected in two ways:
•
NAMUR switching output - Ri approx. 1 kOhm
•
OC - (open collector) low-resistance switching output with PNP technology
Switching values
CAUTION!
The switching outputs can only be operating if the power supply is applied to terminals I+ and I-.
M10 switching outputs
1
NAMUR terminal connection
2
Isolated switching amplifier
3
PNP technology terminal connection
4
Power supply U
ext.
5
Load R
L
NC contact
NO contact
NAMUR
OC
NAMUR
OC
I [mA]
Switching value reached
< 1
< 1
> 3
max. 100
Switching value not reached
> 3
max. 100
< 1
< 1
MA_H250_R02_en_PRT.book Page 37 Tuesday, September 22, 2009 12:26 PM