SERVICE
5
55
OPTIFLEX X200
www.krohne.com
09/2018 - 4006564001 - AD IECEX OPTIFLEX x200 R01 en
5.4 OPTIFLEX 2200: Replacement of the signal converter
You can replace the signal converter of an OPTIFLEX 2200 level transmitter that has an Ex
approval that agrees with certificate of conformity IECEx DEK 11.0060X. Obey this instruction:
•
Send an order for the device model that is related to the process connection installed on your
site.
Refer to the installation procedures in the handbook. The data (temperature, voltage etc.) given
in these supplementary instructions agrees with the new device configuration. Make sure that
you also obey the limits of the process connection installed on your site.
5.5 OPTIFLEX 1300: Replacement of the signal converter
You can replace the signal converter of an OPTIFLEX 1300 level transmitter that has an Ex
approval that agrees with certificate of conformity IECEx KEM 06.0024X. Obey these instructions:
•
Send an order for the device model that is related to the process connection installed on your
site.
•
If your first device was made before June 2009, you must also attach an adaptor. Use the spare
parts list in the handbook to order the OPTIFLEX 1300 adaptor with the new signal converter.
Refer to the installation procedures in the handbook. The data (temperature, voltage etc.) given
in these supplementary instructions agrees with the new device configuration. Make sure that
you also obey the limits of the process connection installed on your site.
DANGER!
Devices with Ex i approvals:
Devices with Ex i approvals:
Devices with Ex i approvals:
Devices with Ex i approvals: Make sure that you use an intrinsically-safe barrier and electrical
wires with the correct parameters. This data is given on the device nameplate of the new
converter.
DANGER!
Devices with Ex i approvals:
Devices with Ex i approvals:
Devices with Ex i approvals:
Devices with Ex i approvals: Make sure that you use an intrinsically-safe barrier and electrical
wires with the correct parameters. This data is given on the device nameplate of the new
converter. Make sure that the signal converter was not installed in Zone 0 or Zone 20.