Handbook OPTIFLEX 1300 C
OPTIFLEX
1300
C
58
Function (Fct.)
Input Range
Description
C.3.1.0
Output 1 (OP1)
function
Level, level
volume/mass, distance,
interface level*, interface
distance*, interface
volume, ullage
volume/mass, layer or
layer volume.
Level
Pick the output function from the list. This
is independent of the measurement
function being displayed.
C.3.2.0
OP1 4 mA setting
0 m/m³/kg to 20 mA
setting (item C.3.3.0) of
output function (item
C.3.1.0) selected.
0 m/m³/kg**
Assigns a measurement value to 4 mA
C.3.3.0
OP1 20 mA setting
4 mA setting (item
C.3.2.0) to max value
defined by output
function (item C.3.1.0)
selected.
Dependant on output
function**
Assigns a measurement value to 20 mA
C.3.4.0
OP1 Output Range
3.8-20.5 mA-NAMUR or
4-20 mA.
3.8-20.5 mA-NAMUR
Sets the effective range of current output
1 with or without over-run.
C.3.5.0
OP1 Error handling
3.6 mA, 22 mA or Hold.
22 mA
Defines the behavior of the current output
1 in case an error occurs.
C.3.6.0
OP1 HART address
0 to 15.
0
Any HART address greater than 0 will
activate HART Multidrop mode (current
output fixed at 4mA).
C.4.0.0 Output
2
(passive)
You can set the output function for
analogue output 2 (passive) and scale
the current values. Optional output.
C.4.1.0
Output 2 (OP2)
Function
Level, level
volume/mass, distance,
interface level*, interface
distance*, interface
volume*, ullage volume/
mass, layer* or layer
volume*.
Interface level*
The output function can be picked from
the list. The function assigned to output 2
is independent of the function being
displayed.
C.4.2.0
4 mA setting
0 m/m³/kg to 20 mA
setting (item C.3.3.0) of
output function (item
C.3.1.0) selected.
0 m/m³/kg**
Assigns a measurement value to 4 mA.
C.4.3.0
20 mA setting
4 mA setting (item
C.3.2.0) to max value
defined by output
function (item C.3.1.0)
selected.
Dependant on output
function**
Assigns a measurement value to 20 mA.
C.4.4.0
Output Range
3.8-20.5 mA-NAMUR or
4-20 mA.
3.8-20.5 mA-NAMUR
Sets the effective range of current output
2 with or without over-run.
Summary of Contents for optiplex 1300 c
Page 1: ......
Page 49: ...Handbook OPTIFLEX 1300 C 49 OPTIFLEX 1300 C 1 Volume measurement of liquids...
Page 50: ...Handbook OPTIFLEX 1300 C OPTIFLEX 1300 C 50 2 Volume measurement of solids...
Page 51: ...Handbook OPTIFLEX 1300 C 51 OPTIFLEX 1300 C 3 Mass measurement of liquids or solids...
Page 62: ...Handbook OPTIFLEX 1300 C OPTIFLEX 1300 C 62 Finding the advanced setup menu...
Page 95: ...Handbook OPTIFLEX 1300 C 95 OPTIFLEX 1300 C Note...