For initial set up, we strongly recommend the use of the relevant manuals in addition!

     System Configuration

2

100...230VAC (-15% / +10%), 22VA

Diameter range and rail versions

24VDC (-55% / +30%), 12W

Small

DN15...100 / 0.5...4"

DN200...1250 / 8...50"

    Small

    Medium

DN50...400 / 2...16"

DN200...4000 / 8...160"

1

Sensor cable connections

2

I/O connections

3

Mains supply connection

11/2021 - 4008317002 - OPTISONIC 6300 F/W R02  en

1

2

Ultrasonic clamp-on flowmeter for liquids

Installation, assembly, start-up and maintenance may only be performed by appropriately trained personnel. 
Check the nameplate for correct operating conditions.

Quick Start

Quick Start

OPTISONIC 6300 F/W

    General

Device nameplate

1  Electrical connection

For use in hazardous areas, special codes and regulations are applicable. Instruments must not be connected to 
power supply before reading instructions described in the supplementary manual.

This instrument complies with requirements of Low Voltage Directive. Instruments must not be connected to 
power supply before reading instructions described in the manual. 

Check the device nameplate to ensure that the device is delivered 
according to your order.

The responsibility as to the suitability, intended use and corrosion resistance of the used materials against the 
measured fluid of this device rests solely with the operator.

All work on the electrical connections may only be carried out with the power disconnected. Take note of 
the voltage data on the nameplate! Observe the national regulations for electrical installations!

Special conditions to be observed:

● For ambient and process temperatures, specific product and electrical data, see Ex manual or certificate

Observe without fail the local occupational health and safety regulations. Any work done on the electrical 
components of the measuring device may only be carried out by properly trained specialists.

● The enclosures of the flow sensor and/or cable box shall be protected against electrostatic charging

Check the Ex data on nameplate in case of 
an Ex version (if applicable)

Check for damage

● For dimensions and details of the flameproof joints, the manufacturer shall be contacted

● The tensile strength of the special fasteners is at least 700 N/mm² (property class A2-70 / A4-70)

    Electrical connections signal converter

Power supply - grounding

● All connection cables are fixed and installed correctly so adequate protection against possible damage is 
guaranteed

2  3

3

● Only for connection to a separately certified UFC 300 F/…Ex flow converter

● The instructions provided with the product shall be followed in detail to assure safe operation

1

Ex ► Type Examination Certificate: KIWA 17ATEX 0034 X / KIWA 18ATEX0007 X

Ta = -40…+70°C / -40…+158°F 

Medium

The device must be grounded in accordance with 
regulations in order to protect personnel against electric 
shocks.

Tp = -40…+200°C / -40…+392°F 

Maximum ambient and process temperatures 

are depending on version (e.g liner material , 

DN size), temperature and protection class 

and maximum surface temperature of sensor.

  General

24VAC/DC (AC: -15% / +10%; DC: -25% / +30%), 
22VA or 12W

Large

Refer to the manual for connection of Ex (/i ) acc. to 
NAMUR

For devices used in hazardous areas, additional safety 
notes apply; please refer to the Ex documentation.

1

2

3

Preferred measuring modes