4
ELECTRICAL CONNECTIONS
22
OPTISWIRL 4200
www.krohne.com
08/2016 - 4005002601- AD OPTISWIRL4200 Ex-II2GD R01
4.5 Flow sensor circuits (remote version only)
Observe the following points when connecting the flow sensor to the signal converter:
•
Use only the supplied connecting cable (max. length 50 m / 164 ft).
•
Before connecting or loosening the equipotential bonding cable, ensure there are no
differences in potential.
•
Connect the connecting cable shield to the equipotential bonding of the hazardous area in the
wall bracket. On the flow sensor side, the shield must be carefully isolated from the earth
(test voltage 500 V
eff
) and connected via the terminal end to the corresponding connector on
the terminal block.
•
The terminal compartments of the flow sensor circuits are supplied with a bridge between
the internal PA connection and the terminal with the designation "gnye". This connection
must not be separated.
The flow sensor circuit is designed in protection type intrinsically safe Ex ia II C.
Figure 4-1: Connection of remote version
1
Terminal connection of flow sensor
2
Terminal connection of signal converter
3
Terminal end pair shielding of flow sensor
4
Filler wire pair shielding (protected with heat shrink tubing)
5
Fork clamp pair shielding on signal converter side
6
Heat shrink tubing