6 Setup
OPTISWITCH 3200 C • NAMUR
31357-EN-210702
6 Setup
6.1 General information
The figures in brackets refer to the following illustrations.
On the electronics module you will find the following display and
adjustment elements:
•
Potentiometer for adjustment of the density range (1)
•
DIL switch for mode adjustment - min./max. (2)
•
Simulation key (3)
•
Signal lamp (6)
6.2 Adjustment elements
4
5
6
3
1
2
Simulation
NAMUR IEC 60947-5-6
VB60N
Fig. 12: Electronics and connection compartment - NAMUR output
1 Potentiometer for adjustment of the density range
2 DIL switch for characteristics reversal
3 Simulation key
4 Ground terminal
5 Connection terminals
6 Control lamp
With the potentiometer you can adapt the switching point to the solid.
It is already preset and must only be modified in special cases.
By default, the potentiometer of OPTISWITCH 3200 C is set to the
right stop (> 0.02 g/cm³ or 0.0008 lbs/in³). In case of very light-weight
solids, turn the potentiometer to the left stop (> 0.008 g/cm³ or
0.0003 lbs/in³). OPTISWITCH 3200 C will thus be more sensitive and
can detect light-weight solids more reliably.
For instruments detecting solids in water, these settings are not ap-
plicable. The density range is preset and must not be changed.
Function/Configuration
Electronics and connec-
tion compartment
Adjustment of the density
range (1)