5
OPERATION
56
OPTISYS SLM 2100
www.krohne.com
01/2017 - 4002737304 - MA OPTISYS SLM 2100 R04 en
C4, extended setup
C3.5
control input 3
Settings of the corresponding control input.
C3.5.1
mode
This function allows to define the different modes of the corresponding
control input.
Options:
•
off
•
maintenance
C3.5.2
invert signal
This function allows to define how the control input is activated.
Options:
•
off (control input is activated when the contact is closed at the input)
•
on (control input is activated when the contact is opened at the input)
C3.6
relay 1
Settings of the corresponding relay.
C3.6.1
mode
This function allows to set the relay as "off", "status output" or "limit
switch".
C3.6.2
inversion
This function allows to define how the relay is activated.
Options:
•
off (control input is activated when the contact is closed at the input)
•
on (control input is activated when the contact is opened at the input)
C3.6.3
status
This function allows to set the status as "error in device", "application error"
or "out of specification" (this menu is displayed only if "status output" is
selected in C3.6.1).
C3.6.3
threshold
This function allows to specify a threshold value of the sludge level (this
menu is displayed only if "limit switch" is selected in C3.6.1). Default 1 meter
C3.6.4
hysteresis
This function allows to specify a hysteresis value of the sludge level (this
menu is displayed only if "limit switch" is selected in C3.6.1). Default 0 meter
C3.6.5
direction
This function can define if the limit switch is set as above or below the
threshold value (this menu is displayed only if "limit switch" is selected in
C3.6.1).
C3.7
relay 2
Settings of the corresponding relay (all submenus and options are identical
with relay 1, except that they start with C3.7 instead of C3.6).
Menu level Designation / function
Settings / descriptions
This submenu allows to set the initial parameters for commissioning of the meter.
C4.1
maximum depth
Definition of the maximum depth.
Default: 0 meter
For further information refer to
Definition of positions and zones
on
page 59
C4.2
start position
Definition of the start position.
Default: 0 meter
For further information refer to
Definition of positions and zones
on
page 59
C4.3
blind zone
Definition of the blind zone. Default:
0 meter
For further information refer to
Definition of positions and zones
on
page 59
C4.4
current incl. blind zone
Definition if blind zone is included in
the current output calculation of
height/depth. Default: no
For further information refer to
Definition of positions and zones
on
page 59
C4.5
rake height
Definition of the rake height. Default:
0 meter
For further information refer to
Definition of positions and zones
on
page 59
C4.6
cleaning
Settings of the cleaning unit.
Menu level Designation / function
Settings / descriptions
Summary of Contents for OPTISYS SLM 2100
Page 85: ...NOTES 8 85 OPTISYS SLM 2100 www krohne com 01 2017 4002737304 MA OPTISYS SLM 2100 R04 en ...
Page 86: ...8 NOTES 86 OPTISYS SLM 2100 www krohne com 01 2017 4002737304 MA OPTISYS SLM 2100 R04 en ...
Page 87: ...NOTES 8 87 OPTISYS SLM 2100 www krohne com 01 2017 4002737304 MA OPTISYS SLM 2100 R04 en ...