03/2012 - 4001904901 - HB OPTIWAVE 5200 R01 en
www.krohne.com
25
OPTIWAVE 5200 C/F
INSTALLATION
3
Figure 3-19: Horizontal cylindrical tanks
1
The device is installed without a stilling well. There are multiple reflections. Refer to the CAUTION! that follows.
2
The device is installed in a stilling well and measures correctly.
CAUTION!
If the device is installed in horizontal cylindrical tank that contains a high dielectric constant
liquid without a stilling well, do not put it on the tank centerline. This will cause multiple
reflections and the device will not measure accurately. Use the 2.3.12 Multiple Reflections
function in Supervisor > Basic Parameters to keep the effects of multiple reflections to a
minimum. For more data, refer to Function description on page 58 (2. Supervisor).
Bypass chambers
Installation next to tanks containing one liquid and foam
•
The top process connection of the bypass chamber must be above the maximum level of liquid.
•
The bottom process connection of the bypass chamber must be below the lowest measured level of liquid.
Installation next to tanks containing more than one liquid
•
The top process connection of the bypass chamber must be above the maximum level of liquid.
•
The bottom process connection of the bypass chamber must be below the lowest measured level of liquid.
Summary of Contents for OPTIWAVE 5200 C/F
Page 67: ......