2.7.3 Installation requirements for concrete roofs
2.8 Installation recommendations for liquids
2.8.1 General requirements
CAUTION!
Install coaxial probes in clean liquids that are not too viscous.
Figure 2-17: Installation on a concrete roof
1
The diameter, d, of the hole must be greater than the thickness, t, of the concrete.
2
If the thickness, t, of the concrete is greater than the diameter, d, of the hole, install the device in a recess.
Figure 2-18: Installation recommendations for liquids
1
The electromagnetic (EM) field generated by the device. It has a radius of R
min
. Make sure that the EM field is clear of
objects and product flow. Refer to the table that follows.
2
If there are too many objects in the pool, install a stilling well.
3
Keep the probe straight. If the probe is too long, shorten the probe length. Make sure that the device is configured with
the new probe length. For more data on the procedure, refer to the handbook.
4
Empty space. Refer to the table that follows.