6 Setup with the integrated display and adjustment unit
SU 600 • 4 … 20 mA signal conditioning instrument
30652-EN-150129
•
Overflow protection
: Relay is switched off when the max. level is
exceeded (safe currentless state), relay is switched on again when
the level falls below the min. level (switch-on point < switch-off
point)
•
Dry run protection
: Relay is switched off when the level falls
below the min. level (safe currentless state), relay is switched on
again when the max. level is exceeded (switch-on point > switch-
off point)
→
To adjust the on and off switching points of relay 1, set the func
-
tion switch to position [
1
] or [
2
], enter the switching points for ON
or OFF and save your settings. If necessary, proceed in the same
way with relay 2 (position [
3
] or [
4
]).
2
1
3
off (on)
on (off)
o n
o n
o f f
o f f
t
L E D
Fig. 7: Relay modes
1 Filling height
2 Mode overfill protection
3 Mode dry run protection
Scaling means converting the measured value into a certain param-
eter and unit. The indication can then show the volume in litres e.g.,
instead of the percentage value. Indication values from -9999 to
+9999 are possible.
1. First of all, determine the max. indicating range and the number of
decimal places after the decimal point -- max. four decimal places
Scaling
Summary of Contents for SU 600
Page 1: ...Operating Instructions SU 600 4 20 mA signal conditioning instrument Document ID 30652...
Page 30: ...30 Notes SU 600 4 20 mA signal conditioning instrument 30652 EN 150129...
Page 31: ...31 Notes SU 600 4 20 mA signal conditioning instrument 30652 EN 150129...
Page 32: ...Subject to change without notice 30652 EN 150129...