OPERATION
6
47
WATERFLUX 3070
www.krohne.com
06/2016 - 4004999701 - MA WATERFLUX 3070 - R01 en
6.3.2 Menu overview
Access levels to the menu:
Items only available with full menu access
Items available in the service menu (and with full menu access)
Software version 5.0.2_
No.
Function
Default
Description
Access control
Access control
Access control
Access control
1
Access control
0
Full menu access
AMR mode (Automatic Meter Reading)
AMR mode (Automatic Meter Reading)
AMR mode (Automatic Meter Reading)
AMR mode (Automatic Meter Reading)
2
AMR mode
0
Off
3
AMR digits
8
Use all digits
Counters and flow rate
Counters and flow rate
Counters and flow rate
Counters and flow rate
10
Counter:
unit of volume
01
m
3
11
Counter:
number of decimals
99
Automatically
12
Counter:
multiplier value
99
Automatically
13
Show forward counter
0
Off
14
Show reverse counter
0
Off
15
Flow rate:
unit of volume / time
0102
m
3
/h
16
Flow rate: unit of time
99
Automatically
17
Show flow rate
0
Off
Pulse output
Pulse output
Pulse output
Pulse output
20
Pulse output A
0
Off
21
Pulse output B
0
Off
22
Pulse output A and B:
phase shift
0
90
°
offset
23
Pulse output A and B:
pulse width
5
5 ms
24
Pulse output A and B:
pulse value
00.100
Automatically
25
Pulse output A and B:
pulse generation
99
Automatically
30
Pulse output C
0
Off
31
Pulse output C:
unit of volume
01
m
3
32
Pulse output C: pulse width
5
5 ms
33
Pulse output C: pulse value
00.100
Automatically