9

English

2  English

2.1  Basic instructions

Mobile heating unit HM200 are the result of

tenth of years of experience and intensif deve-

lopment work. We are convinced of handing you 

over a high-quality product.
Nevertheless, the heater must be installed, set 

into operation and tested by measurings corre-

sponding to the respective circumstances by a 

specialist.

Read the instruction handbook carefully, prior 

to installing and comissioning the heater.

Attention

All details stated, refering to installation and 

setting into operation must be effected and 

observed carefully in order to grant an economic 

operation free of malfunctions. 

The space heaters are proved in accordance to 

EN1020 and must be equipped by oil burners, 

proved in accordance with EN267 or gas burners 

in accordance with EN676 with an automatic 

control box, which is permitted for this space 

heater.

Technical changes in the sense of product  

improvement reserved.

2.2  Designated use

Everywhere, where heat is needed or to keep 

free of icing or for an agreable climate Kroll mobil 

heating units are the ideal partners:

•  Majors construction sites
•  Tents
•  Storage halls
•  Supplementary or intermediary heater
•  as replacement in case of break-down of 

the mobile heating unit

Inappropriate use

These space heaters are not suitable for 

household use and must be used only by 

persons who have been instructed about their 

operation.

Attention

Responsibility

In order to qualify for the guarantee, the device 

must be installed and commissioned by a 

specialist. The settings are to be recorded in a 

measurement certificate.

 

Please fill out all the points of the guarantee

form correctly, sign, and send it to Kroll. Please 

note that in case of missing measuring values no 

guarantee certificate will be issued.

 

The guarantee will only be granted if a regular 

servicing is carried out at least once a year and 

in accordance with the Kroll operating instruc-

tions. The results must be recorded in the appli-

cable measurement certificates.

 

The usual guarantee period granted on our 

device covers 24 months after delivery - the date 

of the invoice being decisive.

The fan must cool the combustion chamber 

and heat exchanger -Danger of over-heating! 

Do not switch off electrical supply and master 

switch until the space heater has cooled down.

Attention

Non-compliance invalides the factory  

guarantee

It is strictly prohibited to add any petrol. 

If the pump pressure is set at a higher value 

in order to get the heater started up in case of 

low ambient temperatures, the device will be 

overheated as soon as the ambient and oil tem-

peratures are increasing. This will entail cases of 

damage, excluding any warranties. 

In case of deflagrations, an analysis of the fuel oil 

used should be made available, and the installa-

tion of the device should be verified by an expert.

 

Any warranties will equally lapse if EL fuel oil 

according to the DIN Standard No. 51 603-1 is 

used at temperatures below + 4° C or if winter 

diesel is used below stipulated temperatures. 

Do not use any additives.

Damage during transport

Transport damages must be noted on the for-

warders receipt and signed by the driver. Your 

dealer must be notified of any technical damage 

before the appliance is assembled and set into 

operation. The heater is only be started up after 

competent repair.

Any cases of consequential damage due to the 

failure of the device during operation will be 

excluded from liability.

Attention

Summary of Contents for HM100

Page 1: ...Betriebsanleitung Instruction handbook Notice d instruction HM200 Mobile Heizzentrale Mobile heating unit Centrale mobile de chauffage Originalbetriebsanleitung 001939 17 Mai 2017...

Page 2: ......

Page 3: ...elements 14 2 8 3 Burner after sales Service 14 2 8 4 Servicing 15 2 8 5 Tighten the V belt 15 3 Fran ais 16 3 1 Instructions de base 16 3 2 D signation 16 3 3 Instruction de base de s curit 17 3 4 M...

Page 4: ...Transportsch den m ssen auf dem Spediti onsannahmeschein vermerkt und vom Fahrer quittiert werden Technische St rungen m ssen unverz glich Ihrem H ndler angezeigt werden Ger t erst nach Instandsetzung...

Page 5: ...ek hlt ist F r einen sicheren Betrieb der Ger te ist es dringend notwendig das von Kroll angebo tene Abgaszubeh r einzusetzen 1 4 Aufstellung Die mobile Heizzentrale nur auf feuersiche rem Boden aufst...

Page 6: ...ornstein festgelegt werden kann z B Einzug eines Edelstahlrohres Ausschleudern des Kami nes Montage eines Saugzuggebl ses etc Abgasthermometer Die Heizungsanlage sollte zur berwachung der Abgastempera...

Page 7: ...nforderung eintragen Hinweis Die Steuerung der Heizzentrale und des Brenners erfolgt ber den Wahlschalter L ften AUS Heizen mit Raumthermostat Heizen ohne Raumthermostat Wenn die ltemperatur unter 4 C...

Page 8: ...etzt Nach Erreichen der Raumtemperatur schaltet der Brenner ab Nach Unterschreiten der einge stellten Raumtemperatur schaltet der Brenner automatisch wieder ein Au erbetriebnahme Kleinsten Wert am Rau...

Page 9: ...Schrauben oben und unten l sen die 2 Schrauben links und rechts am Blinddeckel entfernen danach den Blinddeckel nach oben schieben und unten nach au en wegziehen Wartung Gem 9 der Heizungsanlagenveror...

Page 10: ...s erneuert werden 1 8 5 Spannen wechseln der Keilriemen Keilriemenspannung ist in Ordnung wenn durch geringen Druck auf den vorderen Keilriemen ein maximales Ma von 15 mm eingehalten werden kann Um La...

Page 11: ...he guarantee form correctly sign and send it to Kroll Please note that in case of missing measuring values no guarantee certificate will be issued The guarantee will only be granted if a regular servi...

Page 12: ...supply plug when the heater has entirely cooled down For a safe operation of the apparats it is absolutely necessary to use the Kroll flue gas accessories 2 4 Location The mobile heating unit is only...

Page 13: ...ed steel tube centrifuge of the fire place assembling of a suction blower etc Flue gas thermometer The heating plant should have a flue gas thermo meter to control flue gas temperature the hotter the...

Page 14: ...the demand for garanty Attention Ventilation Heating with room thermostat Heating without room thermostat The mobile heating unit and burner are controlled by the selector switch Ventilation OFF Heat...

Page 15: ...the case may be De commissioning Set the selctor switch to 0 The fan will repea tedly start on in order to remove residual heat from the space heater Do not switch off at the master switch while hea t...

Page 16: ...t exchanger and the heat exchanger seal the individual pockets of the heat exchanger have to be cleaned using a brush and a vacuum cleaner 2 8 3 Burner after sales Service Unscrew the 4 screws above a...

Page 17: ...ombustion chamber of unburned heating oil must take place before the reset but ton is pressed again Kroll recommends taking out a service contract The mobile heating unit must not be modified or modif...

Page 18: ...du Diesel d hiver au dessous de la temp rature prescrite Dommage au cours du transport Les dommages survenus au cours du transport doivent tre not s sur le bon de reception et sign s par le conducteu...

Page 19: ...voir de fioul La tem p rature du fuel s l ve plus de 4 C Pour tous les travaux effectu s sur l installation lectrique enlever pr alable ment la prise d alimentation Retirer la prise d alimentation du...

Page 20: ...recalibrage de la chemin e extracteur etc Thermom tre de fum es Afin de surveiller la temp rature des fum es l installation de chauffage devrait tre quip e d un thermom tre de fum es Plus les temp ra...

Page 21: ...on Ventilation Chauffage avec thermostat d ambiance Chauffage sans thermostat d ambiance La commande du centrale mobile de chauffage et du br leur s effectue par le commutateur Ventilation Arr t Chauf...

Page 22: ...arr te Mise hors service R gler le commutateur sur position 0 Un d marrage rep t du ventilateur pour but d eliminer la chaleur r siduelle l int rieur de l appareil Ne pas couper le courant l aide de l...

Page 23: ...re une fois par an Nous recommandons de conclure un contract de service avec une entreprise autoris e 3 8 5 Service apr s vente br leur Le br leur devrait tre v rifi et r gl au moins une fois par an E...

Page 24: ...jamais tre lubrifi s Attention filtrante et la buse de br leur doivent tre rempla c es Ces travaux ne doivent tre effectu s que par le service apr s vente ou bien par un professionnel agr Apr s un ess...

Page 25: ...200 Abgasmassenstrom Volllast Flue gas mass flow full load D bit massique de gaz d vacuation pleine charge kg s 0 0817 NOX Klasse NOX Class NOX Cat gorie 3 Nennluftvolumenstrom bei 45K Nominal air de...

Page 26: ...enner Gas burner Br leur gaz R30 AE WLE RG30 N KE25 D se Nozzle Gicleur 3 5 gph 60 S Steinen Druck lpumpe Pressure oil pump Pressure de la pompe fuel 14 bar 6 2 mbar Ma A Measure A Dimension A 20 mm M...

Page 27: ...25 Einzelteile Component parts Nomenclature 6 Einzelteile Component parts Nomenclature...

Page 28: ...6 1 21 lfilter Oil filter Filtre fuel 000783 10 1 22 Heiz lentl ftung Fuel daeriator Da riateur du fuel 012793 1 23 Dichtung Seal Joint 011688 2 24 Blende Shield Ecran 001933 1 25 Ventilatorwand Venti...

Page 29: ...Heat exchanger cover Capot d changeur de chaleur 002792 2 66 Dichtung Seal Tendeur 012770 2 67 Auslasstasche Outlet element Post changeur 001646 1 68 Verst rkungsplatte Reinforcing rib Profil de renf...

Page 30: ...1 2 3 4 5 6 K1 B6A F3 h Z1 l max Absicherung 16A 5x2 5mm Zuleitung 7x0 75mm Brenner Einstufig PE X1 B6A F2 1 2 S2 40 C 1 2 B1 X1 X2 H1 X1 X2 H2 X1 X2 H3 3x1 0mm Heizung S2 Raumthermostat S1 Wahlschalt...

Page 31: ...achbetrieb auszuf llen Messwert lbrenner Gasbrenner D senbest ckung D se ldurch satz Pumpen ber druck Gasart Gasd se Flie druck Filter eingang Flie druck D se mbar Gasdurchsatz m h 1 Stufe 2 Stufe l h...

Page 32: ...d work shop Test data Oil burner Gasburner Nozzle type and number Oil flow rate Express pressure pump Type of gas Gas nozzle Flow pressure filter inlet Flow pressure nozzle mbar Gasconsumption m h 1st...

Page 33: ...le Br leur Fuel Polycombustible Br leur gaz Type du gicleur D bit fuel Pression pompe Type de gaz Gicleur gaz Pression l entr e au filtre inlet Pression gicleur mbar D bit gaz m h 1 allure 2 allure l...

Page 34: ...HM200 32 32 11 EG Konformit tserkl rung EG Deglaration of conformity EG D gclaration of conformit...

Page 35: ...33...

Page 36: ...ufacturer leads to expiration of any right to warranty Furtheron our Conditions of Sales and Delivery are valid Technical modification for product improvement are subject to change without notice Tout...

Reviews: