BCU 560, BCU 565 · Edition 02.16
50
10 Fault signalling
Fault message (blinking)
DISPLAY
Description
Burner 1 flame simulation
01
Flame simulation/flame signal before ignition
No flame after safety time 1
02
No flame formation to end of 1
st
safety time
Flame failure during flame proving period 1 t
FS1
03
Flame failure during burner 1 operation
04
Flame failure during operation
Too many remote resets
10
Remote reset activated > 5 × in 15 min.
Too many restarts
11
> 5 restarts in 15 minutes
Controller enable output (terminal 56)
20
Controller enable output incorrectly connected/
supplied with power from an external source
Simultaneous activation (terminals 51 and 52)
21
“Maximum capacity” and “Ignition capacity” posi-
tion feedback from butterfly valve set simultane-
ously
Actuator wiring (terminals 52 – 55)
22
Faulty wiring of terminals 52 – 55
Actuator feedback (terminal 52)
23
Maximum or ignition capacity is not constantly
signalled back to terminal 52
Simultaneous Min./Max. bus command
24
“Open actuator” and “Close actuator” bus signals
set simultaneously
Non-fail-safe parameters (NFS) inconsistent
30
NFS parameter range is inconsistent
Fail-safe parameters (FS) inconsistent
31
FS parameter range is inconsistent
Mains voltage
32
Operating voltage too high/low
Faulty parameterization
33
Parameter set contains illegal settings
Air valve control defective
34
Incompatible bus module
35
Power module defective
36
Relay contact error
Fuse defective
39
Device fuse F1 is defective
Inlet valve(s) leaking
40
Leak found on inlet valve
▼