background image

GFK · Edition 05.19

EN-3

 

The filter pad should be changed at a pressure 

gradient ≥ 20 mbar (8 "WC).

Pressure test points on the cover:  
GFK 15 to 100:  
inlet side: Rp 1/8 pressure test nipple,  
outlet side: Rp 1/8 pressure test nipple.  
GFK 125 to 250:  
inlet side: Rp 1/8 plug,  
outlet side: Rp 1/8 plug.  
GFK 15T to 100T:  
inlet side: Rp 1/8 plug,  
outlet side: Rp 1/8 plug. 

p

 max. = 20 mbar

Cleaning or replacing the filter pad

 1 

Shut off the gas supply.

 2 

 

 3 

 

 4 

 

 5 

 

 6 

 

Clean or replace the filter pad.

 7 

 

 8 

 

Fit the filter pad into the groove in the cover.

 9 

 

 10 

 

 11 

 

Tighten screws in a crosswise fashion and pay 

attention to the torque, see table:

type

torque [nm]

GFK 15

5

GFK 20

5

GFK 25

8

GFK 32

8

GFK 40

8

GFK 50

8

type

torque [nm]

GFK 65

8

GFK 80

20

GFK 100

20

GFK 125

60

GFK 150

60

GFK 200

80

GFK 250

80

 

When replacing the filter pad, the gas-filled space in 
the GFK is opened. Therefore, check for tightness 
once the filter pad has been reinstalled, see  page 
2 (Tightness test).
 

teCHnICAL DAtA

Gas type: natural gas, town gas, LPG (gaseous), 

biogas and air.
Max. inlet pressure p

u

:  

GFK 15 to 250: 1 bar,  
GFK 15R to 65R, GFK 15TN to 100TN: 4 bar 
(60 psig),  
GFK 40F to 100F: 6 bar. 

Ambient temperature: -15 to +80°C (5 to 176°F).  

Continuous operation at high temperatures acceler-
ates the ageing of elastomer materials. 

Version to DIn 3386  

Housing 

GFK 15 to 100 made from AlSi.  
GFK 125 to 250 made from sheet steel. 
GFK..R: Rp internal thread connection to ISO 7-1.  
GFK..F: flanged connection to ISO 7005, PN 16.  
GFK..N: NPT internal thread.  
GFK..A: ANSI 150 flanged connection. 
Filter pad: polypropylene fleece (standard 50 μm).

Pressure test points on the cover

GFK 15 to 100:  
inlet side: Rp 1/8 pressure test nipple,  
outlet side: Rp 1/8 pressure test nipple. 
GFK 125 to 250:  
inlet side: Rp 1/8 plug,  
outlet side: Rp 1/8 plug. 
GFK 15T to 100T:  
inlet side: Rp 1/8 plug,  
outlet side: Rp 1/8 plug. 

DesIGneD LIFetIMe

This information on the designed lifetime is based on 

using the product in accordance with these operat-
ing instructions. Once the designed lifetime has been 
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in 
accordance with EN 13611 for GFK: 10 years. 

You can find further explanations in the applicable 

rules and regulations and on the afecor website  (www.
afecor.org).
 

Summary of Contents for GFK 65

Page 1: ...ons can also be found at www docuthek com Explanation of symbols 1 2 3 a b c Action Instruction Liability We will not be held liable for damage resulting from non observance of the instructions and non com pliant use Safety instructions Information that is relevant for safety is indicated in the instructions as follows DANGER Indicates potentially fatal situations WARNING Indicates possible danger...

Page 2: ...TALLATION CAUTION Incorrect installation Please observe the following to ensure that the GFK is not damaged during installation and operation Dropping the device can cause permanent damage In this event replace the entire device and associated modules before use Installation position as required in hori zontal or vertical pipework recom mended housing cover to the side The housing must not be in c...

Page 3: ...let pressure pu GFK 15 to 250 1 bar GFK 15R to 65R GFK 15TN to 100TN 4 bar 60 psig GFK 40F to 100F 6 bar Ambient temperature 15 to 80 C 5 to 176 F Continuous operation at high temperatures acceler ates the ageing of elastomer materials Version to DIN 3386 Housing GFK 15 to 100 made from AlSi GFK 125 to 250 made from sheet steel GFK R Rp internal thread connection to ISO 7 1 GFK F flanged connectio...

Page 4: ... product GFK with product ID No 0063AU1408 complies with the requirements of the listed Directives and Standards Directives 2014 68 EU PED Regulation EU 2016 426 GAR The relevant product corresponds to the tested type sample The production is subject to the surveillance proce dure pursuant to Regulation EU 2016 426 Annex III paragraph 3 Elster GmbH Scan of the Declaration of conformity D GB see ww...