3 .2 Program sequence
The TEST starts with the waiting time t
W
.
Once the waiting time t
W
has elapsed, the tightness
control TC checks the pressure p
Z
between the inlet
valve V1 and the outlet valve V2.
Program A
If the pressure p
Z
is greater than half the inlet pressure
p
u
/2, valve V2 is OK.
V2 opens for the fixed opening time t
L
of 2 s and the test
vol- ume is discharged. V2 closes again. During the
measurement time t
M
, the TC checks the pressure p
Z
between the valves again. If the pressure p
Z
is now less
than half the inlet pressure p
u
/2, valve V1 is also OK.
Program B
If the pressure p
Z
is less than half the inlet pressure p
u
/2,
valve V1 is OK.
V1 opens for the fixed opening time t
L
of 2 s and the
test volume is supplied. V1 closes again. If the pres-
sure p
Z
is now greater than half the inlet pressure p
u
/2,
valve V2 is also OK.
PZ
V1
p
u
2
V2
p
u
p
Z
TEST
START
t
W
Program
A
+
p
Z
>
p
u
–
Program
B
2
V2
OK
V1
OK
V2
V1
t
L
= 2 s
t
L
= 2 s
V2
V1
t
M
t
M
p
Z
>
p
u
+
2
–
V1
OK
p
Z
>
p
u
V1
V2
2
+
V2
OK