FCU 500, FCU 505 · Edition 02.17
117
Parameters
12 .8 .4 Function of terminal 67
Parameter 72
BCU
V1
BCU
V1
FCU 500
µC
54 55
53
1
+24V
M
4
(FCU)
L1
67
L1
67
The terminal can be assigned the function “BCU ready”.
The FCU is informed via terminal 67 that there are suf-
ficient burner control units for operation. If there is no
“BCU ready” signal, the FCU will perform a safety shut-
down or fault lock-out, depending on the function se-
lected in parameter 72.
Parameter 72 = 0: Off
Parameter 72 = 1: BCU ready; if not, safety shut-down
If there is no feedback signal, a safety shut-down will be
performed, see page 145 (Safety shut-down).
Parameter 72 = 2: BCU ready; if not, fault lock-out
If there is no feedback signal, a fault lock-out will be
performed, see page 145 (Fault lock-out).
Parameter 72 = 2: AND with emergency stop (termi-
nal 46)
Parameter 72 = 3: AND with air
min.
(terminal 47)
Parameter 72 = 4: AND with air flow monitoring (termi-
nal 48)
Parameter 72 = 5: AND with gas
min.
(terminal 49)
Parameter 72 = 6: AND with gas
max.
(terminal 50)
12 .8 .5 Function of terminal 68
Parameter 73
The terminal can be assigned the function “Contactor
feedback”.
Parameter 73 = 0: Off
Parameter 73 = 1: contactor feedback, see page 127
(Safety interlock output)
Parameter 73 = 2: AND with emergency stop (termi-
nal 46)
Parameter 73 = 3: AND with air
min.
(terminal 47)
Parameter 73 = 4: AND with air flow monitoring (termi-
nal 48)
Parameter 73 = 5: AND with gas
min.
(terminal 49)
Parameter 73 = 6: AND with gas
max.
(terminal 50)