FCU 500, FCU 505 · Edition 02.17
130
Project planning information
14 .8 Parameter chip card
The parameter chip card must be installed in the unit for
the FCU to operate. The parameter chip card contains
the valid parameter settings for the FCU. If an FCU is
replaced, the parameter chip card can be removed from
the old unit and inserted into the new FCU. The FCU
must be disconnected from the electrical power supply
for this purpose. The valid parameters are then adopted
by the new FCU. The old device and the new FCU must
have an identical type code.
14 .9 System leak tightness check
V3
DG
V3
pu
Vp1
PZ
pu
2
V1
V2
PZ
Vp2
V3
DG
V3
15
N
A pressure switch DG
V3
can be connected between V3
and terminal 15 of the FCU for the controlled pressure
reduction of the test volume V
p2
via a relief valve.