FCU 500, FCU 505 · Edition 02.17
74
Parameters
12 Parameters
Any changes to parameters will be saved to the parameter chip card.
Name
Parameter
Value range
Description
Factory default settings
10
0
1
2
Off
With safety shut-down
With fault lock-out
2
12
0
1
2
Off
With safety shut-down
With fault lock-out
2
13
0
1
2
Off
With safety shut-down
With fault lock-out
2
15
0
1
2
Off
With safety shut-down
With fault lock-out
2
Safety time during operation tSB
19
0; 1; 2
Time in seconds
1
20
0
1
2
3
Off
STM function
STL function
STM and STL function
FCU..H0 = 0
FCU..H1 = 2
22
1
2
3
Type K
Type N
Type S
1
Temperature difference limit value
23
10 – 100
Temperature in °C
50
STM limit value (high temperature operation)
24
650 – 1200
STM limit value (high temperature
operation) in °C
750
STL/FSTL limit value (system protection)
25
200 – 1600
STL/FSTL limit value in °C
350
26
10 – 100
Temperature in °C
50
Pre-purge during high temperature operation
27
0
1
Off
On
1
29
0
1
Off
On
1
30
0 – 6000
Time in seconds
0
31
0
1
2
Off
With safety shut-down
With fault lock-out
2
▼