FCU 500, FCU 505 · Edition 02.17
76
Parameters
Name
Parameter
Value range
Description
Factory default settings
47
0 – 60
Time in minutes during which the burner
must reach its operating position
60
51
0
1
2
3
4
Off
Tightness test before start-up
Tightness test after shut-down
Tightness test before start-up and after
shut-down
Proof of closure function
0
52
2
3
4
V2
V3
V4
3
53
1
2
3
V
p1
V
p1
; pressure reduction via V3
V
p1
+ V
p2
; pressure reduction via V3
1
54
0
1
In standby
Upon start-up
0
55
0 – 6000
Time in seconds
0
56
3
5 – 25
30 – 3600
Time in seconds
(in 5 s steps)
(in 10 s steps)
10
57
3
5 – 25
30 – 3600
Time in seconds
(in 5 s steps)
(in 10 s steps)
10
59
2 – 25
Time in seconds
2
60
2 – 25
Time in seconds
2
62
0 – 3600
Time in seconds
0
63
0 – 250
Time in seconds
0
65
0 – 25
Time in seconds
0
67
0
1
Unlimited
5 minutes
1
▼