FCU 500, FCU 505 · Edition 02.17
102
Parameters
12 .4 .15 Controller enable time limit
Parameter 47
Can only be programmed on FCU..F1 and FCU..F2.
Parameter 46 = 1 must be selected.
The FCU is informed by the burner operating signal (ter-
minal 4) that the burners have started up.
BCU
V1
BCU
V1
FCU 500..F1
µC
54 55
53
1
67
(BCU..F0)
+24V
L1
M
4
+24V
4
54 55
53
M
To ensure that the furnace control unit does not end-
lessly wait for the enable signal, a time (0 to 60 min.)
can be defined using parameter 47 by which the burn-
ers must reach their operating position. If no feedback
signal is received during this time, the FCU performs
a fault lock-out. The time does not start until the mini-
mum enable time has elapsed.